Optional Modules - Notifier RP-1001 Installation Manual

Deluge - preaction control
Table of Contents

Advertisement

Installation Procedure
2SWLRQDO0RGXOHV
20
www.PDF-Zoo.com
The fire control panel has two
module connectors — J5 and J8.
Three modules are available for the
panel and they can be used in any
combination, including duplicate
modules. The corresponding option
jumper must be cut before instal-
lation of an optional module.
Note: Optional 4XLM module for
an RZA-4X Annunciator must be
installed on J8 only. The 4XTM and
4XZM modules can be installed in
either location.
Insert the two stand-offs (provided)
into the holes located on the right-
side edge of the main board.
Carefully align the pins on the main
board with J1 and/or J2 on the
optional board. Insert screw
through the optional board until it
is secured on the stand-offs.
Affix the terminal identification
labels provided with the optional
modules as shown in Figure 2.9.
Optional Board
(4XZM shown)
(Part # 42050)
Stand-offs
Figure 2.8 Assembling Optional Modules
C
B+ A+ A- B-
B+ A+ A- B-
B+ A+ A- B-
B+ A+ A- B-
TB4
JP 1
NO DACT
DACT
SUPV 2
ALM2
-
-
!%
-
!%
-
Figure 2.7 Selecting Location & Cutting Jumpers
Main
Board
Figure 2.9 Labelling Optional Modules

Optional Modules

Note: If a
4XTM
module is
or
installed in
4XZM
this position,
cut jumper
"OPT1" on
the main
board.
Note: If a
module is
4XTM
installed in
or
this position,
4XLM
cut jumper
or
"OPT2" on
4XZM
the main
board.
RP-1001 15150:F 05/24/2001