General
The cabinet assembly consists of two basic components; the backbox (SBB) and door (DR). All cabinets for the
AM2020/AFP1010 are fabricated from 16-gauge steel.
Cabinet parts are painted Notifier gray or red with navy blue windows.
Provided with the key-locked door are a pin-type hinge, window, two keys, and the necessary hardware to mount
the door to the backbox.
The backbox has been engineered to provide ease-of-entry, with knockouts positioned at numerous points to
simplify conduit installation.
The hinges are field-selectable for either left or right mounting. The door opens 180 degrees.

Product Line Information

Cabinets are available in sizes A through D. The cabinets are identified by product codes CAB-A3 for the
smallest enclosure through CAB-D3 for the largest.
A trim ring (TR) option is available for semi-flush mounting (TR-A3, TR-B3, TR-C3, TR-D3).
A wire channel (WC) option provides a pair of wire trays to neatly route wire between rows in the cabinet. Order
one pair per cabinet row.

Prior To Installation

The doors may be mounted in either a left or right opening configuration; aiding in installation and service when
two control panels are mounted in a confined area or side-by-side (as shown). In this manner the doors may be
opened "barn door" style, creating an open work space. Note that in this type of installation it is necessary to
leave enough space between cabinets to insert a key into the locks on the door frames.

Left Mount

On a left mounted door, the Display Interface
Left
Right
Assembly (DIA) dress panel cannot be opened
Mounted
Mounted
when the door is at less than a 120 degree
Door
Door
angle to the cabinet. If you are using the left
mounting option, be sure that the door can
open at least 120 degrees. This is especially
important if the cabinet is to be mounted in a
closed area, such as a closet or utility room.
NOTE
The two hinges and the two alignment tabs
should be attached to the backbox before any
equipment is mounted in the backbox. See the
Door Assembly Instructions section.