Programming Key for Figure 1.3-6 (Cont)
ACM-16AT/-32A Annunciator:
Annun. Pt.
AXXP1
AXXP2
AXXP3
AXXP4
MM Security Access Monitor:
Address: LXXMYY (Installer specified).
Type ID: SACM
Control-By-Event: (Zaa*)
Custom Label: Installer Option (describe specific
Tracking: Yes—Each unsecured state will
Annunciator: Yes
Annunciator Point: AXXP4

Zone Programming

1. Zone Boundary: Must be less than Zad* and greater than or equal to Zac*.
2. Zone to Which All Instant Security Modules
Are Mapped
Zone: Zaa*
Type ID: FZON
Control-By-Event: ( )
Custom Label: Instant Group
Annunciator: No
3. Zone Activated Upon Arming System
Zone: Zab*
Type ID: FZON
Control-By-Event: ( )
Custom Label: Arming Zone
Annunciator: Yes
Annunciator Point: AXXP2
4. Zone Activated When Entry/Exit Door Is Open
Zone: Zac*
Type ID: FZON
Control-By-Event: ( )
Custom Label: Tenant A Entry/Exit
Annunciator: No (Not required).
4-14
www.PDF-Zoo.com
Type ID
AMON
AZON
AMON
AMON
location of module).
be printed when the print option is
enabled.
No—The first unsecured state will
be printed when the print option is
enabled (restorals will not print un-
til reset at Central Station - short
condition only).
MM = CM
Group Interface:
A: CM programming:
Address: LXXMYY (Installer specified).
Type ID: CMXC
Control-By-Event: (Zaj*)
Custom Label: Security Group Output
Signal Silence: No
Walk Test: Yes/No (Installer Specified).
Annunciator: No (Not required).
B: MM programming:
Address: LXXMYY (Installer specified).
Type ID: SARM
Control-By-Event: ( )
Custom Label: Installer Specified.
Tracking: Yes—Results in required
knowledgment at Central Station
for every unsecured state. Resto-
ral is automatic.
No—Results in required acknowl-
edgment at Central Station for first
unsecured state only (until reset at
Central Station - short condition
only).
Annunciator: No (Not required).
5. Zone Activated When Any Instant Module Is Vi-
olated and the System Is Armed
Zone: Zad*
Type ID: RZON
Control-By-Event: AND(Zaa* Zab*)
Custom Label: Installer Specified.
Annunciator: No (Not required).
6. Zone Active for 30 Sec., 30 Sec. After Opening
Entry/Exit Door (Not Dependent on Door Clo-
sure)
Zone: Zae*
Type ID: RZON
Control-By-Event: SDEL(00.00.30 00.00.30 (Zac*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
7. Zone Active 1 Min. After Entry/Exit Door Is
Opened and Left Open
Zone: Zaf*
Type ID: RZON
Control-By-Event: DEL(00.01.00 (Zac*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
a c -
Security 15088:J
10/22/99