3=TDLY
Option 3 from the Partial System Programming submenu allows the programmer to enable/disable Alarm
Verification of detectors, Signal-Silence Inhibit and Signal Cut-out for control modules, as well as setting the
appropriate time delays for these functions. For a full description of these functions, see the Glossary of Terms
and Abbreviations at the end of this manual.
3 = TDLY
Change
Detector
Verification
Time?
No
The following programming example illustrates enabling all three functions:
PRESS@1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM@@@@@
DO@YOU@WANT@TO@CHANGE@THE@DETECTOR@VERIFICATION@TIME?@(Y=YES,N=NO)
DO@YOU@WANT@THE@DETECTOR@VERIFICATION@TIME@ENABLED?@(Y=YES,N=NO)
ENTER@THE@DETECTOR@VERIFICATION@TIME@(5@-@50@IN@1@SECOND@INCREMENTS)
DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@SILENCE@INHIBIT@TIME?@(Y=YES,N=NO)
DO@YOU@WANT@THE@SIGNAL@SILENCE@INHIBIT@TIME@ENABLED?@(Y=YES,N=NO)
ENTER@THE@SIGNAL@SILENCE@INHIBIT@TIME@(1@-@255@IN@1@SECOND@INCREMENTS)
DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@CUT-OUT@TIME?@(Y=YES,N=NO)
DO@YOU@WANT@THE@SIGNAL@CUT-OUT@TIME@ENABLED?@(Y=YES,N=NO)
ENTER@THE@SIGNAL@CUT-OUT@TIME@(1@-@2040@IN@1@SECOND@INCREMENTS)
3-12
www.PDF-Zoo.com

Enable
Detector
Yes
Yes
Verification
Time?
No
Change
Signal Silence
Yes
Inhibit Time?
No
 D }X1X3X
Enter Detector
Verification
Time (5-50 sec)
Enable Signal
Silence Inhibit
Yes
Time
No
Change
Yes
Signal Cut-
Out Time?
No
Enter Signal Silence
Inhibit Time
(1-255 sec)
Enable
Enter Signal Cut-
Signal Cut-
Yes
Out Time?
(1-2040 sec)
No
(Exit Prog Mode)
Programming 15088:J 10/22/99
Out Time
:@3
:@Y
:@Y
:@35
:@Y
:@Y
:@240
:@Y
:@Y
:@600