After entering option 8 from the Partial System Programming submenu, the display will show the ISIB submenu:
PRESS@1=INSTL,2=ANN,3=XINT,4=DACT
1=INSTL - ISIB Installation
This option allows the installation or removal of the Intelligent Serial Interface Board from control panel
memory. The board must still be physically installed or removed from the system to prevent a system trouble
condition. The following programming example illustrates the installation of the Intelligent Serial Interface
Board.
PRESS@1=INSTL,2=ANN,3=XINT,4=DACT
DO@YOU@WANT@TO@CHANGE@THE@INTELLIGENT@SIB?@(Y=YES,N=NO)
DO@YOU@WANT@THE@INTELLIGENT@SIB@ENABLED?@(Y=YES,N=NO)
PROGRAMMING@COMPLETE@@-@@POWER@DOWN@TO@MAKE@APPROPRIATE@CHANGES
See notes in Section 1.1, Partial System Programming.
2=ANN - Annunciator Installation
This option allows the installation or removal of annunciators (EIA-485 devices) from the AM2020/AFP1010
memory. The modules must still be physically installed or removed from the system to prevent a system
trouble condition. The following programming example illustrates the installation of annunciator module 1.
PRESS@1=INSTL,2=ANN,3=XINT,4=DACT
ENTER@THE@ANNUNCIATOR@NUMBER@TO@CHANGE@(1@-@32)
IS@ANNUNCIATOR@01@TO@BE@INSTALLED@IN@SYSTEM?@(Y=YES,N=NO)
ENTER@20@CHARACTER@CUSTOM@LABEL
DO@YOU@WANT@TO@CHANGE@ANOTHER@ANNUNCIATOR?@(Y=YES,N=NO)
PROGRAMMING@COMPLETE@@-@@POWER@DOWN@TO@MAKE@APPROPRIATE@CHANGES
* The SCS-8 and SCS-8L firmware has been updated in conjunction with Software Release 2.8. The new SCS
firmware is not backward compatible with older revisions of software.
3=XINT - External Interface Parameters
This option allows the programmer to change the parameters associated with the external interface port.
The following example illustrates enabling all associated parameters.
PRESS@1=INSTL,2=ANN,3=XINT,4=DACT
DO@YOU@WANT@TO@CHANGE@THE@ACS
*
DO@YOU@WANT@THE@ACS
*
DO@YOU@WANT@TO@CHANGE@THE@INTELLIGENT@SIB@ADDRESS?@(Y=YES,N=NO)
*
ENTER@THE@INTELLIGENT@SIB@ADDRESS@(0@-@249)@ @@@@@@@@@@@@@@@@@@@@@@@@@@@
*
DO@YOU@WANT@TO@CHANGE@THE@MIB-W@THRESHOLD@FOR@CHANNEL@A?@(Y=YES,N=NO)
*
ENTER@THE@MIB-W@VALUE@THRESHOLD@FOR@CHANNEL@A@(H=HIGH,L=LOW)
*
DO@YOU@WANT@TO@CHANGE@THE@MIB-W@THRESHOLD@FOR@CHANNEL@B?@(Y=YES,N=NO)
*
ENTER@THE@MIB-W@VALUE@THRESHOLD@FOR@CHANNEL@B@(H=HIGH,L=LOW)
*
DO@YOU@WANT@TO@CHANGE@MIB@DATA@PORT@USAGE?@(Y=YES,N=NO)
DO@YOU@WANT@TO@USE@BOTH@MIB@DATA@PORTS?@(Y=YES,N=NO)
DO@YOU@WANT@TO@CHANGE@ACK/SIL/RES@LOCKOUT@SETTINGS?@(Y=YES,N=NO)
DO@YOU@WANT@ACK/SIL/RES@LOCKED@OUT@AT@THE@PANEL?@(Y=YES,N=NO)
*
DO@YOU@WANT@ACK/SIL/RES@RE-ENABLED@DURING@LAN@COMM@FAULT?@(Y=YES,N=NO)
*
* These items are NOTI•FIRE•NET™ specific functions and are only programmed when a SIB-NET is used.
• During an upload/download, the fire protection capability of the AM2020/AFP1010 is enabled (it is limited for download). To
reduce the risk of incompatible databases, the programmer should NEVER program any parameters into the control panel
while an upload/download is in progress.
• To communicate over the external interface, the annunciator modules MUST first be disconnected since both functions
use the same serial port.
• When an Intelligent SIB Board is changed from one address to another, the CCBE is lost. If the address is changed back
to the previous address, CCBE will return.
Programming 15088:J 10/22/99
www.PDF-Zoo.com
@@@@@@@@@@@@@@@@@@@@
D }X1X8X1X
D }X1X8X2X
D }X1X8X3X
PORT@UPLOAD/DOWNLOAD?@(Y=YES,N=NO)
PORT@UPLOAD/DOWNLOAD@ENABLED?@(Y=YES,N=NO)
NOTES
@@@@@@@@@@@@@@@@@@
:@ANNUNCIATOR@ONE
:
:@1
:@Y
:@Y
:@2
:@1
:@Y
:@N
:@3
:@Y
:@Y
:@Y
:@249
:@Y
:@L
:@Y
:@H
:@Y
:@Y
:@Y
:@Y
:@Y
3-23