Security System Diagrams And Programming Keys; Simplest Security System; Central Station - Notifier AM2020 User Manual

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

Security System Diagrams and Programming Keys

The following figures illustrate the minimum system requirements for various configurations of the AM2020/
AFP1010 and associated peripherals.
Refer to Table 1.1-1 in the introduction to this chapter for monitor and control module information. Refer to the
XP5 Series Transponder Manual listed in the Related Documentation Chart of this manual for connection
information for the XP5 modules. Refer as well to the Product Installation Documents 15984 (RKS-S Remote
Keyswitch) and 15456 (STS-1 Security Tamper Switch) for connection information on these devices.
Refer to the Glossary section of this manual for descriptions of the terms used in this section.
The following system requirements are illustrated in Figure 1.3-1. See Table 1.1-1 the introduction to this section
for other monitor module options.
• One AM2020/AFP1010 Control Panel
• One Security Supervisory Protected Area
• One Protected Premises
• One MMX-1 or MMX-101 Monitor Module, Security Devices (minimum security equipment).
Motion Detector
Contact Switch
MM Security Area Monitor
Pull Station
Smoke Detector
Programming Key for Figure 1.3-1
MM Security Area Monitor:
Address:
Type ID:
Control-By-Event: ( )
Custom Label:
Tracking:
Annunciator:
Annunciator Point
Mapping (Optional): AxxPyy
Security 15088:J
10/22/99
www.PDF-Zoo.com
TENANT A
AREA 1
(Perimeter)
Key
Figure 1.3-1 Simplest Security System
LXXMYY (Installer specified).
SARM
Installer Specified (describe location of module).
Yes - Results in required acknowledgment at Central Station for every unsecured state.
Restoral is automatic.
No - Results in required acknowledgment at Central Station for first unsecured state only (until
reset at Central Station - short condition only).
No (not required).
Yes (if annunciator mapping desired)
47K End-of-Line Resistor (A-2143-00)
1
Signaling Line Circuit
(SLC)
Normally open security
switch (listed)
Normally closed security
switch (listed)
MMX-1 or MMX-101
Security Area Monitor
(See Fig 1.3-7 for MMX-101 wiring
polarity)
SLC to LIB at

Central Station

AM2020/AFP1010
Central Station
4-7