Remote Printers; Printer Configuration - Notifier AM2020 User Manual

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

The AM2020/AFP1010 can employ PRN Remote
Printers. This printer provides a hard-copy printout of
all status changes within the system and time-
stamps the printout with the current time-of-day and
date. The PRN provides 80 columns of data on
standard 9 inch by 11 inch tractor-feed paper.
Installation
Remote printers require 120 VAC, 50/60Hz primary
power. A secondary power source (battery backup) is
not provided; the use of a separate Uninterruptable
Power Supply (UPS) 50 watt minimum, UL listed for
Fire Protective Signaling is recommended. A UPS is
required for NFPA 72 Proprietary Protected Premises
Receiving Unit applications.
Connection between the control panel and PRN is
provided through an EIA-232 interface on the Serial
Interface Board. An installer provided cable must be
assembled for connection to the printer's EIA-232
port. Refer to Figure 5.3-2 for wiring instructions.
Using a special print feature, the PRN allows all
information programmed into the panel to be printed
out (including system configuration and addressable
device parameters).
The PRN is factory programmed.
Plug this DB-25 connector into the
EIA-232 Port of the printer.
1-88
www.PDF-Zoo.com
NOTE
PRN
Remote
Printer
nc

Printer Configuration

Refer to the documentation supplied with the PRN for
instructions on the printer's menu controls. Set the
printer's options as follows:
L/R ADJUST:
FONT:
LPI:
ESC CHARACTER:
BIDIRECTIONAL COPY:
CG-TAB:
COUNTRY:
AUTO CR:
LANGUAGE:
AUTO TEAR:
COLOR OPTION:
FORMLEN:
LINES:
STANDARD:
CPI:
SKIP:
EMULATE:
I/O:
BUFFER:
SERIAL:
BAUD:
FORMAT:
PROTOCOL:
CHARACTER SET:
S1. ZERO:
AUTO LF:
MENLOCK:
PAPER:
BIN 1:
BIN 2:
SINGLE:
PUSH TRA:
PULL TRA:
PAP ROLL:
PAPOPT:
50 feet (15.24 meters)
(typical)
Wiring distance limited
by cable capacitance.
See EIA-232E standard.
SIB (Connector P3)
1
Twisted Pair
2
3
Twisted Pair
4
• Outputs are power limited but not supervised.
• Make connections with overall foil/braided-shield
twisted pair cable.
• Near Letter Quality (NLQ) mode cannot be used on
this printer.
0
HS DRAFT
6 CPI
ESC
ON
GRAPHIC
E-USA ASCII
OFF
ENGLISH
1S
NOT INSTALLED
6 LPI=60
EXECUTIVE 10.5"
10 CPI
0.5"
EPSON
36K FOR PRN-4
40K FOR PRN-5
2400
7 BIT, EVEN, 1 STOP
XON/XOFF
STANDARD
ON
OFF
ALL
12/72"
12/72"
12/72"
12/72"
12/72"
12/72"
NO
SIB-2048A
or
SIB-NET
EIA-232 Reference
Transmit to Printer
EIA-232 Reference
Receive From Printer
NOTES