Change Alarm and Pre-Alarm levels

This option lets you change the Alarm and Pre-Alarm levels of any addressable detector in the system.
To do so, follow these steps.
1.
From the "Alter Status" menu select option 2 - Alarm/Pre-Alarm:
2W
Press
Det. Alarm/Prealarm level, type address D(nnn), then Enter
STATUS CHANGE
Alarm/Prealarm level
2.
Enter the address of the detector you wish to change. For example, change alarm and Pre-Alarm
levels for detector 102 on SLC 1 to Alarm Level 4 & Pre-Alarm Level 2.
1d102Wa5p2W
Press
STATUS CHANGE
Alarm/Prealarm level
D102 sens. at level 5, Prealarm at level 3, Enter AxPx to change, Esc. to Abort
D102 now set at new Alarm level 5 and new Pre-alarm level 2

Clear the Verification Counter

Clear Verification lets you clear the verification counter for all the addressable detectors in the system:
3W
Press
STATUS CHANGE
Clear verify count

Clear the Entire History Buffer

Clear History lets you clear the entire History buffer:
4W
Press
************** History Clear ***************