Pager
The Pager mode must be enabled when a compatible pager is connected to the auxiliary printer port.

Modem

If enabled, the following remote device (CRT) functions are inhibited: ACK STEP, SIGNAL SILENCE, SYSTEM
RESET, PROGRAMMING, and ALTER STATUS. This option must be employed when a modem is used to
receive signals from an off-premise device or when the keyboard is to remain attached to the CRT in a system that
is not configured and operated as a Proprietary Fire Alarm System. See the TPI-232 manual.

NAM

The NAM-232 is used to tie a remote FACP to the NOTI•FIRE•NET™ via telephone lines. If the NAM is
enabled, the following options are automatically programmed as indicated:
• Terminal Supervision = Enabled
• Terminal Status Line = Enabled
• Receiving Unit Mode = Enabled
• Event Reminder = Disabled
• Reports Redirected to Terminal = Enabled
• Modem = Disabled
This special application only supports the ACKNOWLEDGE, SIGNAL SILENCE, and SYSTEM RESET
network functions and is intended for Protected Premises Fire Alarm System (Local) use only. Local use of a
CRT, printer or other 232 device from the remote FACP is prohibited. No other system network functions can
be implemented due to system contraints. For more information refer to the NAM-232 for Use With AM2020/
AFP1010 Manual, Document 50424.

Rapid Polling

The AM2020/AFP1010 has the option to utilize a rapid polling algorithm to process certain monitor modules on
a priority basis. When used properly, this can result in a much faster response from fire alarm call points (pull
stations) and security devices. If Rapid Polling is enabled, the first 20 module addresses on each LIB SLC
loop are polled more frequently than the other addresses and should be used for high priority input devices
when using this feature. However, as a consequence all other SLC addresses will be polled less frequently. XPM-
8 circuits and output devices (CMX and XPC-8 circuits) should not be assigned addresses in the rapid polling
range.

Supervisory Module ACS Reporting

If selected for reporting, activation of modules with the Software Type ID SUPR or SPSU will cause the primary
(top) LED to light instead of the secondary (bottom) LED for an ACS Annunciator Point. This feature must be
enabled for proper transmission of supervisory signal transmission with ADEMCO contact ID mode on a UDACT
communicator.
Programming 15088:J 10/22/99
www.PDF-Zoo.com
3-27