The NOT operator inverts the state of the operand
(activated to deactivated OR deactivated to activated).
NOT(Z2)
The control module will remain activated UNTIL
the operand comes into alarm.
IF Software Zone 2 is in alarm,
THEN this control module will be deactivated.

XZONE

For Cross Zone operation, the XZONE
counting operator may be used.
XZONE(Z23)
IF ANY combination of two or more initiating
devices (L1D1, L1D2, L1D3, L1D4)
that have been programmed (Control-By-Event)
to this software zone (Z23) come into alarm,
THEN this control module will be activated.

NOT

L1D1
L1D4
(Z2)
Z2
L1M1
CMX
NOT(Z2)
L1D2
L1D3
(Z23)
(Z23)
(Z23)
Z23
L1M3
CMX
XZONE(Z23)
Programming 15088:J 10/22/99
L1D4
(Z23)