Troubles; Section Five - Notifier AM2020 User Manual

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

Section 5.1 Trouble ................. with SLC Loop Devices
The following example illustrates the format used to display device trouble conditions:
Detectors:
FIXED PHOT D
FIXED THER D
HEAT(ANALOG)
ION DUCT DET
SMOKE (ION)
SMOKE ION HP
SMOKE ION LP
SMOKE(COMBO)
SMOKE(PHOTO)
Device Status
Software Zone
The first zone that the
device was mapped to
during programming.
For Detectors:
DET FAILED TEST
DEVICE DISABLED
DRIFT TOLERANCE
INVALID REPLY
LOW CHAMBER VAL
MAINTENANCE REQ
PRE-ALARM ALERT
VER COUNT OVFLW
The piezo sounder will sound steadily for unacknowledged trouble conditions.
2-24
www.PDF-Zoo.com

Section Five

Troubles

Device Type (relates to Software Type ID):
Modules:
ACCESS MONTR
ALARMS PEND
AREA MONITOR
CMX CONTROL
CMX FORM C
CONTROL
DACT CONNECT
EQUIP MONITR
FORMC MANUAL
FORM C RELAY
GENERAL PEND
GN ALARM
GN ALARM EVC
TROUBL@SMOKE(PHOTO)@@COMPUTER@ROOM
Z087@MAINTENANCE@REQ@@04:32P@03/01/00@124
Type of Trouble:
For Modules:
DEVICE DISABLED
INVALID REPLY
OPEN CIRCUIT
POINT TROUBLE
SECURITY ALARM
SECURITY ALERT
GN ALARM FORC
GN SUPR FORC
GN TRBL FORC
GN WAT FORC
GN WATER FLW
MON NORM CLD
MON PULL STA
MONITOR
MONITOR PAGE
NON ALARM
NON ALM MON
PAGE
POWER (CONV)
Time and Date
Hour:Minute Month/Day/Year
SECURITY NO COM
SECURITY TAMPER
SHORT CIRCUIT
SPRNKLR TROUBLE
SUPRVSRY SIGNAL
NOTE
PULL STATION
SMOKE (CONV)
SPEAKER
SPRNKLR MNTR
SPRVSRY MNTR
SYSTEM MONTR
TELEPHONE
TRBL MONITOR
TRBLS PEND
TROUBLE
TROUBLE FORC
WATER FLOW
Custom Device Label
that was entered during
programming.
Device Address
in the range 01-99.
SLC Loop Number
in the range 1-9,
with 0=Loop 10.
Operating 15088: J 10/22/99