Notifier AM2020 User Manual page 250

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

Table A-2 (Continued)
Type of Circuit
Common
FFT-7/FFT-7S Fire Fighter's
Telephone Riser
Telephone to an XP Transponder XPC-
(FFT to XPC or
8 module or an XP5-C Transponder
XP5-C)
circuit.
Individual
XP Transponder XPC-8 module fed
Telephone
from an FFT-7/FFT-7S: employs phone
Notification
jacks APJ-1 and FPJ; Fireman's
Appliance Circuits
Handset FHS-1; Fireman's Handset
(XPC to Telephone
Enclosures FHE-F and FHE-S.
Jacks)
Individual
XP5-C Transponder circuit fed from an
Telephone
FFT-7/FFT-7S: employs phone jacks
Notification
APJ-1 and FPJ; Fireman's Handset
Appliance Circuits
FHS-1; Fireman's Handset Enclosures
(XP5-C to
FHE-F and FHE-S.
Telephone Jacks)
ACT-2 output to AA-30/AA-30E, AA-
100/AA-100E, or AA-120/AA-120E
input.
RM-1/RM-1SA output to AA-30/AA-
30E, AA-100/AA-100E, or AA-120/AA-
120E input.
Low level Audio
Riser
AMG-1/E output to AA-30/AA-30E,
AA-100/AA-100E, AA-120/AA-120E,
ACT-1 or RM-1/RM-1SA input
High level Audio
AA-30/AA-30E output to ACT-2 input
Riser
XP Transponder XPP-1; Dual Form-C
Alarm and Trouble Relays
XP Transponder XPR-8: Eight Form-C
relays or four Dual Form-C relays.
CMX-1: One Form-C relay
Form-C Dry
Contacts
CMX-2: One Form-C relay
XP5-C Transponder: 5 Form-C relays
A-6
www.PDF-Zoo.com
Devices/Ratings
24 VDC (nominal), 1-Vrms max. 800 Hz to 2800 Hz. Seven (7)
telephone handsets active at one time max including Master
Telephone. Supervised/power-limited. Two-wire circuit
supervised via 27K ELR, Part # R-27K (N-ELR for Canada).
Optional return loop for 4-wire circuit. Max wiring resistance
(including individual telephone zone to last handset) permitted is
40 ohms. 10,000 ft. (3048 m) max wiring distance at 12 AWG
(3.25 mm
No telephone jack maximum per circuit. Two-wire circuit
supervised via a 47K ELR, Part # R-47K (N-ELR in Canada).
No outboard ELR for four-wire supervised circuit. Max
resistance due to wiring is 40 ohms from FFT-7 to termination of
the telephone circuit. Power limitation is a function of the signal
source employed. Telephone handset ring signal is provided
with this module.
No telephone jack maximum per circuit. Two-wire circuit
supervised via a 47K ELR, Part# R-47K (N-ELR in Canada).
Max resistance due to wiring is 40 ohms from FFT-7 to
termination of the telephone circuit. Power limitation is a function
of the signal source employed. Telephone handset ring signal is
not provided with this module.
NFPA Class B circuit, power-limited 3.5 VRMS max., 50 mA
max.. Monitored for integrity at destination (listed amplifier).
Maximum wiring distance 200 ft (61 m) at 18 to 12 AWG (0.75
to 3.25 mm
recommended when connecting to more than one amplifier.
NFPA Class B circuit, power-limited 3.5 VRMS max., 50 mA
max.. Monitored for integrity at destination (listed amplifier).
Maximum wiring resistance from AMG or ACT-2 low-level source
connected at input of RM-1/RM-1SA to farthest AA series
amplifier at output of RM-1/RM1-SA is 40 ohms. Twisted and
shielded wiring recommended when connecting output to more
than one amplifier.
Power-limited/supervised, 40 ohm maximum resistance. 10,000
feet (3048 m) maximum distance at 12 AWG (3.25 mm
wire. Twisted and shielded wiring recommended. Connect
shield to REF A audio source.
Power-limited, 25VRMS, 30 W max., frequency response 800 Hz
to 2800 Hz, two-wire circuit must be monitored for integrity at
destination equipment (listed amplifiers), four-wire circuit is
monitored for integrity at AA-30/AA-30E, 40 ohm maximum wire
resistance.
2 amps resistive @ 30 VDC. One amp inductive (0.6 pf) @ 24
VDC. Not supervised. Power limitation is a function of the
signal source applied.
2 amps resistive @ 30 VDC. One amp inductive (0.6 pf) @ 24
VDC. Not supervised. Power limitation is a function of the
signal source applied.
2 amps resistive @ 30 VDC. One amp inductive (0.6 pf) @ 30
VDC.
2 amps resistive @ 30 VDC. One amp inductive (0.6 pf) @ 30
VDC. Pilot duty: 0.6 amps @ 30 VDC (0.35pf); 0.3 amps @
110 VDC (0.35 pf);0.3 amps @ 120 VAC (0.365 pf).
3 A @ 30 VDC, resistive, non-coded. 2 A @ 30 VDC, resistive,
coded. 0.9 A, 110 VDC, resistive, non-coded. 0.9 A, 125 VAC,
resistive, non-coded. 0.5 A, 30 VDC, inductive (L/R=5ms),
coded. 1.0 A, 30 VDC, inductive (L/R=2ms), coded. 0.5A, 125
VAC, inductive (PF=.35), non-coded.
Circuit Ratings
2
) to last handset.
2
) gauge wire. Twisted and shielded wiring
Connections
FFT-7/FFT-7S Connector P3 Term. 3(+) and 2 (-):
to XPC-8 Connector P3.2 (+), P3.1(-), and/or P4.2
(+) P4.1 (-), P5.2 (+) P5.1(-), P6.2 (+) P6.1(-),
P7.2(+) P7.1(-), P8.2 (+) P8.1(-), P9.2(+) P9.1(-),
P10.2(+) P10.1(-);
to XP5-C,TB1-TB5, EXT-, EXT+ or J1A-J5A.
Optional four-wire redundant return to FFT-7/FFT-7S
Connector P3 Term. 6(+) and 5(-)
to XPC-8 Connector P10;
to XP5-C,TB1-TB5, EXT-, EXT+ or J1A-J5A.
Two-wire circuits (8 telephone circuits on XPC-8
P2): Term 1 (-), 2 (+); 3(-), 4 (+); 5 (-), 6 (+), 7 (-), 8
(+); 9(-), 10 (+); 11 (-), 12 (+); 13 (-), 14 (+); 15 (-),
16 (+).
Four-wire circuits (4 telephone circuits on XPC-8
P2): Term. 1,3
(-), 2,4 (+); 5,7 (-), 6,8 (+); 9,11
(-), 10,12 (+); 13,15 (-), 14,16 (+).
Two-wire circuits (5 telephone circuits) on :
TB1-TB5, B-, B+
ACT-2 pins 3,2, and 1 plug directly into P3.3, P3.2,
and P3.1 respectively of an AA-30/AA-30E, or AA-
120/AA-120E. Additional AA series amplifiers feed
from the first amplifier P3.6 (shield), P3.5, and P3.4
to additional amplifier P3.3, P3.2, and P3.1
respectively.
RM-1/RM-1SA TB5 shield out, TB5 - out, and TB5 +
out to AA series amplifier P3.3, P3.2, and P3.1
respectively or another RM-1/RM-1SA on TB4 shield
in, - in, and + in respectively.
Internal two-wire: AMG-1 P5 to AA Series Amplifier
P2. External two-wire: AMG-1 P4, Terminals 4 (-)
and 5 (+) to AA Series Amplifier P3, Terminals 4 (-)
and 5 (+). External four-wire connection: include
return from AA-30 P8, Terminals 5 (-) and 6 (+) to
2
) gauge
AMG-1 P4, Terminals 1 (-) and 2 (+).
Connect AMG-1 P4 terminals 4 (-) and 5(+) to ACT-
2 AUDIO IN terminals (not polarity sensitive).
Connect AMG-1 P4 Terminals 4(-) and 5(+) to RM-
1/RM-1SA TB4 "IN" terminals (not polarity sensitive)
Use of twisted shielded cable is recommended.
Two-wire: AA-30/AA-30E P8, Terminals 6 and 5 to
ACT-2 "Audio In" terminals (not polarity sensitive).
AA-30/AA-30E Terminal 4 (shield) to ACT-2 "S".
Optional 4-wire return: ACT-2 "Thru" terminals to
AA-30/AA-30E P8, Terminals 3 and 2 (not polarity
sensitive).
Refer to the XPP-1 in the XP Series Transponder
System Manual.
Refer to the XPR-8 in the XP Series Transponder
System Manual.
Power: Term 2 (+), Term 1 (-) Normally Open
contacts use Term 4; normally closed contact use
Term 5: common use Term 6. Break tabs for Form-C
relay.
Power: Term 2 (+), Term 1 (-) Normally Open
contacts use Term 4; normally closed contact use
Term 5: common use Term 6. Break tabs for Form-C
relay.
TB1-TB5, com, N/O, N/C.
Appendices
15088:J
10/22/99

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp1010

Table of Contents