1. Product Description

Bases and Accessories

Several bases, to which the detectors are affixed, are available:
Modules
Control Modules and Monitor Modules provide an interface between the control panel and conventional
notification and initiating devices. Each module can be set to respond to an address with built-in rotary
switches.
Note: For a list of approved notification and initiating devices, refer to the Device Compatibility Document.
Below are descriptions of various addressable monitor modules and control modules used with the
control panel.
Note: A blinking LED on a monitor module indicates communication between the module and the control panel.
18
Technical Manuals Online! - http://www.tech-man.com
B710LP
B501
B501BH
B501BHT
B224RB
B524BI
RA400Z
9
9
0
0
6 7
6 7
8 9
8 9
10
5
10
5
11
11
4
4
8
8
1
1
12
12
3
3
13
13
2
2
1
1
14
14
7
7
0
0
15
15
2
2
TENS
TENS
6 7
6 7
8 9
8 9
5
5
6
6
3
3
4
4
3
3
2
2
5
1
1
4
5
4
0
0
ONES
ONES
ADDRESS
LOOP
LOOP
ADDRESS
ADDRESS
14 15
0
0 1
1
13
2
2
12
3
3
LOOP
11
4
4
10
5
5
9
6
9
6
7
7
8
8
TENS
ONES
Standard U.S. Low-Profile base
Standard European flangeless base
Sounder base, includes B501
Same as B501BH, but includes Temporal Sounder
Low Profile Intelligent relay base
Intelligent isolator base
A Remote Single LED Annunciator that can be wired
directly off of an addressable detector for annunciation of
that detector's alarm status.
Monitor Modules - FMM-1, FZM-1 & FDM-1
Addressable monitor modules for monitoring conventional initiating
devices. The FMM-1 is used for normally open contact alarm
initiating devices, such as manual pull stations, four-wire smoke
detectors, heat detectors, waterflow, security contacts, and supervisory
devices. Use the FZM-1 for specific two-wire smoke detectors in
addition to normally open contacts. The FDM-1 provides two
independent 2-wire IDCs at two separate, consecutive addresses. Wire
supervised IDCs as NFPA Style B (Class B) or Style D (Class A)
circuits. The modules come with a thermoplastic cover for mounting
to a 4-inch square mounting box.
Monitor Module - FMM-101
An addressable module that is functionally similar to an FMM-1
Monitor Module —but offered in a smaller package for mounting
directly in the electrical box of the device being monitored.
Addressable Devices
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002