Group 13: Annunciator Output
Type ID
ACON
AFCM
Group 14: Annunciator Telephone
Type ID
ATEL
Group 15: Annunciator Supervisory
Type ID
ASUP
Group 16: Trouble Module
Type ID
MTRB
Note: This software type can be used to monitor power from an Uninterruptable Power Supply (UPS) under
NFPA 72 Proprietary Fire Alarm Systems applications or to monitor remote Main Power Supply in XP
Transponder systems.
Group 17: Page Module
Type ID
MPAG
Programming 15088:J 10/22/99
www.PDF-Zoo.com
Display Label
Annunciator Point that indicates the state of any CMX Control Module, XPC-8
ANN CONTROL
circuit, XPR-8 relay, or XP5-C circuit mapped to it. This annunciator point can also
be used for manual control of relays, speaker and notification circuits.
Annunciator Point that is not deactivated upon system reset. Used for fan
ANN FORC MAN
control and similar applications only with an FRCM control
device.
Display Label
Annunciator Point that indicates the state of any CMX Control Module or
ANN TELEPHON
XPC-8 or XP5-C circuit configured for telephone operation. This annuncia-
tor point can also control the state (connect/disconnect) of the circuit.
Display Label
Annunciator Point that indicates the state of any SPSU or SUPR module
ANN SUPRVSRY
mapped to it.
Display Label
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit used to
TRBL MONITOR
monitor any trouble contacts external to the system. This module will be ac-
tivated by either an open or a short condition, and produces a POINT
TROUBLE message in the display. A Control-By-Event equation need
not be entered for this type since it only produces a trouble signal, not an
alarm.
Display Label
MMX Monitor Module or an XPM-8 circuit or XP5-M circuit dedicated to a normally
MONITOR PAGE
open switch. Activation of a module with Software Type ID MPAG connects the
remotely located Fire Fighter's Telephone handset to the paging system. This Type
ID is used in conjunction with the PAGE Type ID (RPJ-1 required).