5.11
Setting frequency command characteristics
~ , : VI/II point setting
~ , : RR/S4 point setting
~ : RX point setting
~ :
~ :
~ :
~ : Point 1, 2 setting/ frequency
⇒ For details, refer to Section 7.3.
• Function
These parameters adjust the output frequency according to the externally applied analog signal (0~10Vdc
voltage, 4(0)~20mAdc current) and the entered command for setting an external contact frequency.
5.12
Preset speed operation (speeds in 15 steps)
~
5
~ : Preset speed operation frequencies 8~15
~ : Preset speed operation frequencies 1~15 operation mode
• Function
A maximum of 15 speed steps can be selected just by switching an external contact signal. Preset speed
frequencies can be programmed anywhere from the lower limit frequency to the upper limit frequency .
[Setting methods]
1)Run/stop
Run and stop control is experienced by the operation panel (Default setting).
Title
Note 1: If speed commands (analog signal or digital input) are switched in line with preset speed operations, select the
terminal board using the frequency setting mode selection 1 .
⇒ Refer to 3) or Section 5.5.
2)Preset speed frequency setting
Set the speed (frequency) of the number of steps necessary.
Setting from speed 1 to speed 7
~
Setting from speed 8 to speed 15
~
It sets up, when using the optional circuit board.
: Preset speed operation frequencies 1~7
Function
Command mode
selection
Title
Function
Preset speed operation
frequencies 1~7
Title
Function
Preset speed operation
frequencies 8~15
Adjustment range
: Terminal input enabled
: Operation panel input enabled (including
LED/LCD option input)
: 2-wire RS485 communication input
: 4-wire RS485 communication input
: Communication option input
Adjustment range
~
Adjustment range
~
E-18
E6581445
Example of setting
Default setting
Default setting