Basic System Startup Procedure
1-4-3

Configuration

IMPORTANT
1-4-4

User Test

Safety functions may be impaired and serious injury may occasionally occur.
Before operating the system, perform user testing to confirm that the configu-
ration data of all the devices is correct and that they are operating correctly.
IMPORTANT
10
In this step, transfer the parameters for each device created by the Network
Configurator to the actual device to make the system operative.
Use the Network Configurator to perform the following operations:
1. Download
The parameters set in the Network Configurator's virtual network are trans-
ferred to the actual device and stored in each device.
2. Verification
Verify the safety device settings.
The user confirms that the parameters and safety signatures stored in
each device are correct.
Please refer to the following sections for the operating instructions of the Net-
work Configurator.
• Download
Refer to 3-7 Device Parameters and Properties.
• Verification
Refer to 3-8 Parameter Verification.
• After downloading the device parameters, verify the parameters to con-
firm that the parameters and the safety signature saved in the devices are
correct.
• When selecting Open Only in the Open Type setting for the safety con-
nection, check that the Safety Master and Safety Slave are correctly con-
figured.
In this step, the user himself confirms the program operation and performs
functional tests.
Always perform the user test, because it is the user's responsibility to verify
the system operation. The user test verifies the correctness of all parameters
downloaded to each safety device, as well as each device's safety signature.
To demonstrate that all parameters and safety signatures are correct after
completing the user test, perform a Configuration Lock operation on all of the
safety devices.
Refer to 3-9 Configuration Lock for details on performing a Configuration Lock
from the Network Configurator.
!WARNING
• After configuring all the devices, user testing must be performed to check
if the configuration data and device operation of each device are correct.
User testing is performed to verify the safety signature for each device.
• The configuration must be locked after the user testing has completed.
Section 1-4