5. In the Name Field, input the character string of the CPU Unit's data area address, e.g., 100, W100, or D0.
The following data areas can be set.
CPU Unit's data area
CIO Area
Holding Area
Work Area
DM Area
EM Area
Note
(1) The H, W, D, and E characters can also be input in lower case as h, w, d, and e.
(2) Be sure to input the data area address (such as 100, W100, or D0) directly as a character string.
6. Input the size of the tag in the Size Field, in bytes.
7. Click the Regist Button to register the tag.
The next consecutive data area address will be automatically input in the Edit Tag Dialog Box's Name Field,
so that the next tag can be edited. When necessary, change the address and input a data size. When you
are finished registering tags, click the Close Button.
8. Click the Out - Produce Tab, and click the New Button. The Edit Tag Dialog Box will be displayed, like the
dialog box for input tags, except for the Over Load setting. The Over Load setting determines whether out-
puts are cleared or continue their previous status when outputs are turned OFF with the PLC's output inhibit
function. Output inhibit settings are not required for input (reception) tag sets.
• Follow the output inhibit function: Enabled (default)
Output data is cleared to 0 when a PLC output inhibit occurs.
• Do not follow the output inhibit function: Disabled
Output data maintains its previous status even after a PLC output inhibit occurs.
Address (Text to input in Name Field.)
0000 to 6143
H000 to H511
W000 to W511
D00000 to D32767
Bank 0
E0_00000 to E0_32767
Bank C
EC_00000 to EC_32767
Select Disable or Enable.
Appendix A
309