Specifying the CS/CJ Serial Port -> DRM Unit I/F as the Connection Interface
(Continued from step 3 on the previous page.)
1. When CS/CJ Serial Port -> DRM Unit I/F is selected as the connection interface, the Setup Interface Dialog
Box will be displayed. An example is shown below.
Set each item as described below.
Interface
Network Address
Node Address
CPU Bus Unit Number
Communications Port
Select either one of the following interfaces as the
serial communications mode for the serial communi-
cations port on the CS/CJ-series PLC.
• Peripheral bus (ToolBus)
• Host Link
Enter the FINS network address of the destination
DeviceNet Unit. Enter this address when crossing
the network farther than the serial communications
port of the CS/CJ-series CPU Unit. Enter 0 when not
crossing network layers.
Enter this address when crossing the network farther
than the serial communications port of the CS/CJ-
series CPU Unit. Enter 0 when not crossing network
layers.
Enter the unit number of the DeviceNet Unit (i.e., the
CS1W-DRM21(-V1)) as a CPU Bus Unit (i.e., the
value set on the rotary switches on the front of the
DeviceNet Unit).
• The unit number is between 0 and 15.
Select the COM port on the computer running the
Network Configurator (version 2.@).
• Select from the list of available COM ports.
Appendix A
279