Downloading from a Serial Port on a CS/CJ-series CPU Unit via DRM Unit Interface or
from an Ethernet Unit via CS/CJ ETN-DRM Unit Interface
This section describes how to download data to DeviceNet/Safety devices via a CS/CJ-series PLC.
1. Changing the Message Timer of the CS/CJ-series CPU Unit
(1) Right-click the CJ1 and select Parameter - Edit from the displayed menu.
(2) Select the Message Timer Tab in the Edit Device Parameters Window and set the timer value to
10000 (ms) (i.e., 10 s) for the device to be downloaded from. (It is not necessary to change the node
numbers of devices for which data is not to be downloaded.)