Omron DEVICENET SAFETY - SYSTEM CONFIGURATION 07-2009 System Configuration Manual page 114

Table of Contents

Advertisement

Parameter Verification
IMPORTANT After downloading the configuration data, verify the parameters and check
Note
80
After completing the verification, click the Close Button in the upper left to
close the window.
The following window will be displayed.
If the parameters match, click the Yes Button.
After the verification has been completed, the safety symbol attached to the
device icon in the virtual network will turn green, which indicates that verifica-
tion is done.
With Configurator Ver. 2.0@ or higher, the following dialog box will be dis-
played after the verification has been completed.
Click the Yes Button to automatically lock the device.
whether the parameters saved in the device and the safety signature are cor-
rect.
Note Click the Save Button to save the configuration parameter report in
HTML format. Click the Print Button to print the report.
• After verifying the parameters of all the devices, make sure to save the
network configuration file.
• The Verified configuration parameter symbol ensures that the device
parameters in the network configuration file are correct. This information
is saved in the network configuration file, but not in the device itself.
Therefore, the Verified configuration parameter symbol will not be
attached even though the network configuration is obtained by network
upload from a device that has been already verified.
• If you edit parameters that have been verified, the Verified configuration
parameter symbol will disappear. The device parameters must be verified
again.