Safety Input Parameter Groups - Omron DEVICENET SAFETY - SYSTEM CONFIGURATION 07-2009 System Configuration Manual

Table of Contents

Advertisement

Editing Parameters
4-1-4

Safety Input Parameter Groups

Item
S
Off On Delay
S
Off On Delay
S
Safety Input Channel
Mode
S
Test Source
S
Dual Channel Safety
Input Mode
96
This section describes parameters in the safety input parameter groups.
The safety input parameters are grouped by terminal number.
Settings
0 to 126 ms
Sets the OFF/ON delay time.
(in 6-ms increments)
0 to 126 ms
Sets the OFF/ON delay time.
(in 6-ms increments)
Not used.
The safety input is not used. (External input
device not connected.)
Test pulse from test out Specifies connecting a device with a contact
output in combination with a test output.
When this mode is selected, select the test
output to use for the test source and then set
the test output mode to Pulse Test Output.
When these settings are made, contact
between the input signal line and the power
supply (plus) and short circuits with other input
signal lines can be detected.
Used as a safety input.
Specifies connecting a safety device with a
semiconductor output, such as a light curtain.
Used as a standard
Specifies connecting a standard device (i.e., a
input.
non-safety device).
Not used.
If the channel mode of a safety input is set to
Test Pulse from Test Out, the test output is
Test Output 0
selected for use in combination with the safety
Test Output 1
input. Set the channel mode of the test output
selected here to Pulse Test Output.
Test Output 2
Test Output 3
Single Channel
Specifies using Single Channel Mode.
If Single Channel is selected, the safety input
that would be paired for the dual channel
parameter will also be set to Single Channel
Mode.
Dual Channel Equiva-
Specifies using the Dual Channel Equivalent
lent
Mode with a paired safety input.
Dual Channel Comple-
Specifies using Dual Channel Complemen-
mentary
tary Mode with a paired safety input.
Description
Section 4-1
Default
0 ms
0 ms
Not used.
Not used.
Dual Chan-
nel Equiva-
lent

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet safety

Table of Contents