Omron DEVICENET SAFETY - SYSTEM CONFIGURATION 07-2009 System Configuration Manual page 349

Table of Contents

Advertisement

4. Target node IDs are assigned to devices registered in the Register Device List. This target node ID deter-
mines the location in the originator node PLC of the Target Node PLC Operating Flag, Target Node PLC
Error Flag, Registered Target Node Flag, and Normal Target Node Flag. By default, the target ID is auto-
matically set to the rightmost 8 bits of the IP address. In the example above, the target device's IP address
is 192.168.250.2, so the device number is #002. If a target node ID is duplicated and you want to change
the device number, click the Change Target Node ID Button and change the target ID.
Connections Settings (Editing All Connections)
The connection settings between the originator and all of the target devices selected in the Register Device List
can be edited together in a table. (There is another method in which connections are edited individually.)
1. Select the Connections Tab, and click the Edit All Button. The following Edit All Connections Dialog Box
will be displayed.
The following table describes the various settings in the dialog box.
Setting
Target Device
Selects the target device.
Connection
Any name can be given to the connection (up to 32 characters).
Name
If this field is left blank, a default name will be assigned.
This Connection Name can be used for comments.
Connection I/O
When making tag data links in a CS1W-EIP21 or CJ1W-EIP21, select Input Only (Tag type).
Type
When making tag data links in other devices, select the connection I/O type specified in that
device's EDS file.
Use the Input Only (ID type) setting when another company's node is the originator and does not
support connection settings with the Tag type setting.
In/Out
The connections I/O is automatically displayed based on the selected connection.
• Input Only: Just In is displayed.
• Output Only: Just Out is displayed.
• Output & Input: In and Out are displayed in two levels.
Function