The following table describes the various settings in the dialog box.
Setting
Connection
Assigns a name to each connection.
Name
Connection I/O
Select one of the following connection I/O types according to the target connection.
type
• Input Only (Tag type)
• Output Only (Tag type)
• Input Output (Tag type)
Connection
Selects whether the data is sent in a multicast or unicast. The default setting is multicast.
Type
• Multicast connection:
Select when the same data is shared by multiple nodes. This setting is usually selected.
• Point-to-Point connection:
Select when the same data is not being shared by multiple nodes. In a unicast transmission, other
nodes are not burdened with an unnecessary load.
Packet Interval
Sets the data refreshing interval (packet interval) of each connection between the originator and
(RPI)
target. The interval can be set between 0.5 and 10,000 ms, in 0.5-ms units. The default setting is
50 ms (data refreshed once every 50 ms).
Timeout Value
Sets the time until a connection timeout is detected. The time out value is set as a multiple of the
packet interval (RPI) and can be set to a 4, 8, 16, 32, 64, 128, 256, or 512 multiple. The default set-
ting is 4× the packet interval (RPI).
Input from
Allocates the originator's input (consume) tag set selected for the originator variable (Consume
Target Device
Variable) to the target's output (produce) tag set selected for the target variable (Produce Variable).
Output to
Allocates the originator's output (produce) tag set selected for the originator variable (Produce Vari-
Target Device
able) to the target's input (consume) tag set selected for the target variable (Consume Variable).
Function
Appendix A
317