Programming

6-3

Programming

6-3-1

Workspace

Page Settings
IMPORTANT The page setup cannot be changed if there are any items in the Workspace.
Programming Restrictions
First, set the size of the Workspace. Select File - Page Setup from the menu
bar.
The Workspace will consist of pages of the specified size. Pages can be
added or deleted as required. When printing the program, each page will be
printed at the specified size.
Set the size of the Workspace first using Page Setup.
Items, such as I/O tags and function blocks can be used on each page. The
following restrictions apply.
• The same input tag can be placed on more than one page. The same
input tag, however, can be used only once on each page.
• Each output tag can be used only once, even on different pages.
• When a function block is pasted, it is placed in the same position as the
function block that was copied. When pasting a function block on the
same page, move the source function block.
• Up to 128 function blocks can be used with Pre-Ver. 1.0 NE1A-SCPU01
Controllers and up to 254 function blocks can be used with NE1A-series
Controllers with unit version 1.0 or later (including NE1A-SCPU01-EIP
and NE1A-SCPU02-EIP).
• Up to 128 number jump addresses can be used.
• A maximum of 8 characters can be used for the tag name of the jump
address.
• Up to 32 pages can be added.
• Up to 128 text boxes (comments) can be created.