Editing Parameters for Logic Terminals (DST1-XD0808SL-1)
Setting Output Conditions
The following options will be displayed. (Valid only when the terminal mode
is set to output from logic.)
(1)
(2)
2. Select whether to enable or disable the EDM function.
The options are as follows:
(1) Disable EDM Function
The EDM function is not used.
(2) Enable EDM Function
The EDM function is used. Select a terminal to receive the feedback
signal from an external device. It can be any terminal from IN4 to IN7.
When output from logic is selected as the terminal mode, the following figure
will be displayed for the output condition.
(If a mode other than output from logic is selected, the following figure will be
displayed.)
Click the selection button when the above figure is displayed to enable select-
ing the output condition.
Set an AND operation of the safety input logic configuration result and the
value received from the network (interlock signal).
If multiple AND conditions (e.g., IN0 and IN1) are selected, the following dia-
log box will be displayed.
When the settings have been completed, press the Next Button to display the
following dialog box.