Device Parameters and Properties
74
If you click the Abort Button, the download process will be cancelled (and
consequently, the parameters will not be downloaded to the subsequent
devices).
The error that occurred will be displayed in the Message Pane and the device
in which the error occurred will be displayed in the Error Device List.
The Error Device List displays by device the errors that occurred during
parameter download.
• If the Error Device List shows that a parameter error has been found and
if that error was caused by the I/O Terminal settings, the terminal with the
error will be displayed in the Message Pane. (Refer to the outlined section
in the above diagram.) No alarm will appear in the Error Device List if the
error is not caused by the I/O Terminal settings and the cause must be
found elsewhere.
• If the Error Device List displays an error stating that the TUNID does not
match, click the Get from the actual network Button in the Network
Number Field on the Network Property Dialog Box (see note). The net-
work number for the actual network to be downloaded will be in the
project file data. Click the OK Button to update the network number. Then
execute the download again. Refer to 3-4-2 Network Numbers for details
on network numbers and TUNID.
Note
Select Network – Property or right-click in the Network Configuration Win-
dow and select Property to display the Network Property Dialog Box.
Note
Refer to 8-2 Errors When Downloading for Error Device List errors other than
those listed above, error details, and countermeasures.
Note
The download may take time if the NE1A-series Safety Master is in RUN
mode. The time required for downloads can be reduced by changing to IDLE
mode.