Connection Status Tables; Outline; Connection Status For Dst1 Series - Omron DEVICENET SAFETY - SYSTEM CONFIGURATION 07-2009 System Configuration Manual

Table of Contents

Advertisement

Connection Status Tables

8-1

Connection Status Tables

8-1-1

Outline

8-1-2

Connection Status for DST1 Series

Status
00:0001
Normal communications
01:0001
Safety I/O Connection
Timeout
01:0105
Configuration Owner Error The Safety Slave was configured from a configuration tool or Safety Master at a
01:0106
Output Connection Owner
Error
01:0110
Device Not Configurated
01:0113
No. of Connections Error
01:0114
Vendor ID or Program
Code Error
01:0115
Device Type Error
01:0116
Revision Error
220
If an error occurs when the NE1A-series Controller tries to establish a safety
connection with an NE0A-series Controller, DST1-series Safety I/O Terminal
or an NE1A-series Controller set as a Slave, the 7-segment display will dis-
play the error codes d6, dA, or d5.
Check the status code (error code) shown on the Safety Connection Tab Page
in the Monitor Device Window and take the corresponding countermeasure.
The Safety I/O connection status is normal.
The Safety I/O connection has timed out. Check the following items.
• Do all nodes have the same baud rate?
• Is the cable length correct (trunk lines and branch lines)?
• Is the cable disconnected or slack?
• Is the terminating resistance only on both ends of the main line?
• Is there a lot of noise?
• Is the network bandwidth allocation suitable?
different node address last time. Reset the Safety Slave to the default settings
and download the device parameters again.
Refer to 5-1-2 Setting Safety Connection Parameters for information on config-
uration owners.
The Safety Slave established output safety I/o connections with a Safety Mas-
ter at a different node address last time.
Reset the Safety Slave to the default settings and download the device param-
eters again.
Refer to 5-1-2 Setting Safety Connection Parameters for information on output
connection owners.
The Safety Slave has not been configured. Download the device parameters to
the Safety Slave.
The setting for the number of safety I/O connections exceeds the upper limit
supported by the Safety Slave. Adjust the Safety Connection setting for the rel-
evant Safety Master.
The device data (vendor ID or product code) for the device on the Configurator
and the device used in the actual system does not match.
• Use Safety Slave Verification (Device - Parameter - Verify) to check that the
device in the system and the device registered to the Safety Master match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
The device data (device type) for the device on the Configurator and the device
used in the actual system does not match.
• Use Safety Slave Verification (Device - Parameter - Verify) to check that the
device in the system and the device registered to the Safety Master match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
The device data (revision) for the device on the Configurator and the device
used in the actual system does not match.
• Use Safety Slave Verification (Device - Parameter - Verify) to check that the
device in the system and the device registered to the Safety Master match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
Countermeasure
Section 8-1