0x202E
4
0x2030
4
0x2032
4
0x2034
4
0x2036
4
0x2038
4
0x203A
4
0x203C
4
0x203E
4
0x2040
4
0x2042
4
0x2044
4
0x2046
4
0x2048
4
0x204A
4
0x204C
4
0x204E
4
0x2050
4
0x2052
4
0x2054
4
0x2056
4
0x2058
4
0x205A
4
0x205C
4
0x205E
4
0x2060
4
0x2062
4
0x2064
4
0x2066
4
0x2068
4
0x206A
4
0x206C
4
0x206E
4
Input Frequency Level
PPL Enable
Input Current Abnormal Enable
Reserved
Temperature Derating Enable
Capacitive Reactive Power Compensation
Enable
Reserved
Reserved
Grid Voltage Adjustment Enable
Reserved
Reserved
Reserved
Target voltage
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Constant reactive
Voltage Upper Limit (%)
Voltage Lower Limit (%)
Reserved
THDu Limit (%)
Un!!!balance!!! Limit
Reactive Power Tracking Control Value
Reserved
Reserved
Reserved
Reserved
Low Load Energy-saving Shutdown Mode
Reserved
Reserved
0: 50Hz
1: 60Hz
Default: 50Hz
1: Disable
0: Enable
Default: 1
1: Disable
0: Enable
Default: 1
1: Disable
0: Enable
Default: 1
1: Disable
0: Enable
Default: 1
1: Disable
0: Enable
Default: 1
[100V, 700V]
Default: 230V
Accuracy: 0.1
[-3000.0, 3000.0]
Default: 1
Accuracy: 0.1
[0, 20%]
Default: 7%
[-20%, 0]
Default: 10%
[0, 50]
Default: 0
Advanced
[0, 1]
Default: 0
Advanced
[-3000.0, 3000.0]
Default: 0
Accuracy: 0.1
Generally
[0.0, 100.0] ( 0 means disable )
Default: 0
Accuracy: 0.1
67
Need help?
Do you have a question about the SVG 100 Ultra and is the answer not in the manual?