Summary of Contents for Eaton Power Xpert 9395P-1200
Page 1
Eaton Power Xpert 9395 High Performance (9395P-1200) UPS ® ® 1200 kVA, 1200 kW Installation and Operation Manual For use with Three UPM (675–900 kVA) and Four UPM (1000–1200 kVA) UPS Models...
U.S. Environmental Protection Agency. All other trademarks are property of their respective companies. ECopyright 2016 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
Page 5
................P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 6
................. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 7
..........4-36 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 8
................7-14 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 9
..............P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 10
TABLE OF CONTENTS This page intentionally left blank. viii P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The FI-UPM matches the UPS in style and color. There are two Eaton 9395P-1200 UPS model configurations: Three UPM UPS Three UPM UPS Plus 1 FI-UPM P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPM rated for a maximum of 300 kW (900 kW total maximum for three UPMs) ISBM SECTION UPM SECTION Figure 1‐1. Eaton 9395P-1200 Three UPM UPS P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Protection Agency voluntary program that helps businesses and individuals save money and protect our climate through superior energy efficiency. Learn more at http://www.energystar.gov. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
All UPSs in the distributed bypass system must contain the same number of UPMs. Mixed UPS kVA ratings are not permitted. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
At the completion of the time period, the unit defaults back to Energy Saver mode. If the High Alert command is received during the time period, the timer will be restarted. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
PredictPulse requires a Power Xpert Gateway Card (PXGX) ® connectivity card in an X-Slot communication bay and an Environmental Monitoring Probe (EMP) for battery temperature/humidity monitoring. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPS, but is not required for normal operation. NOTE The Eaton 9395P-1200 system can trip a maximum of six battery cabinets total. This applies to both the 1085 standard and High Rate series batteries. If more than six battery cabinets in total are needed in a separate UPM battery configuration, DO NOT hook up the shunt trips.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
All other countries: Please use the following e-mail for manual comments, suggestions, or to report a technical error in this manual. E-ESSDocumentation@eaton.com 1-10 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
(95 % maximum). Le système n’est pas conçu pour une utilisation extérieure. Toutes les sources d’alimentation doivent être débranchées avant de procéder à l’installation et à l’entretien. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 22
Ne pas installer ni faire fonctionner l’onduleur près d’une source de chaleur au gaz ou à l’électricité. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 23
Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 24
SAFETY WARNINGS This page intentionally left blank. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Table 3‐1 includes the weights of the heaviest cabinet configuration. Actual weights may be less due to the installed configuration. Weights are in kilograms (pounds). P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 29
Maximum Relative Humidity: 95%, non-condensing (see section 3.2.1) NOTE If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supersede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
[73.7] 2444 1029 [96.2] [40.5] 1007 [39.6] Dimensions are in millimeters [inches]. Front Figure 3‐9. Three UPMs Center of Gravity - Front View P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
There is no additional connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral loads. 3-11 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 38
Because of the future upgradability to a fully rated 1200 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 1200 kVA in Table 3‐7 and Table 3‐8. 3-12 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 39
Figure 6‐5 . NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 40
Figure 6‐6 . NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 41
(3) Phases, (1) Ground Minimum Conductor Size AWG or kcmil Number per Phase (each) NOTE Callout letters , and map to Figure 6‐7 . 3-15 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 42
(3) Phases, (1) Ground AWG or Minimum Conductor Size kcmil Number per Phase (each) NOTE Callout letters , and map to Figure 6‐8 . 3-16 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 43
Figure 6‐5 . NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 44
(3) Phases, (1) Neutral, (1) Ground AWG or Minimum Conductor Size kcmil Number per Phase (each) NOTE Callout letters , and map to Figure 6‐7 . 3-18 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 45
Figure 6‐5 . NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 46
(3) Phases, (1) Neutral, (1) Ground AWG or Minimum Conductor Size kcmil Number per Phase (each) NOTE Callout letters , and map to Figure 6‐5 . 3-20 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 47
Figure 6‐5 . NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 48
Tightening further will risk breaking or twisting the stud. Figure 4‐8 through Figure 4‐11 show the location of the intercabinet power cable terminals inside the UPS. 3-22 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 49
UPM AC Input, UPM Battery Input, UPM AC Conical Washer 180500037-080 Output UPM AC Input, UPM Battery Input, UPM AC 180200001-05 Output 3-23 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 50
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3‐20. NOTE Bypass terminations are not applicable to IOM configurations. 3-24 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 51
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground conductor sized in accordance with NEC Table 250.122. Conduit sizes listed are for copper wiring only. 3-25 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 52
Battery Cable Routing: Refer to the notes at the bottom of Table 3‐5 to Table 3‐14 Input/Output Ratings and External Wiring Requirements 3-26 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 53
400 Vac AC Input to Bypass and Output Eaton 9395P-1200/825 (A, B, C, Neutral, Ground) 380 Vac Battery (Common Battery) (Positive, Negative, Ground) 3-27 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 54
The values are the same for 480V, 415V, 400V, and 380V input circuit breakers with 100% breaker ratings for rectifier input (see Table 3‐22). NOTE For the Eaton 9395P-1200 400/415/380V models, the max output is 1100 kW/ 1100 kVA. 3-28 P-164000500 Rev 4 www.eaton.com/powerquality...
Page 55
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current. 3-29 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Ne pas directement brancher les contacts de relais aux circuits du réseau. Une isolation renforcée des réseaux est nécessaire. Read and understand the following notes while planning and performing the installation: 3-30 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 57
Alarm relay wiring should be a minimum of 22 AWG. NOTE On all Eaton 9395P-1200 models that will be fed by a site generator at any time it is recommended to have an “On Generator” sensing input connected and proven functional. This allows the UPS to optimize its operation with the generator.
Les sections de l’onduleur sont lourdes (voir le Table 3‐1). Suivre attentivement les instructions de déchargement et de déballage pour éviter de renverser les armoires, ce qui pourrait causer de graves blessures. 3-32 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 59
Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. MISE EN GARDE! Ne pas installer une armoire endommagée.
Page 60
NOTE While waiting for installation, protect the unpacked cabinets from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. 3-34 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
C A U T I O N Do not tilt cabinets more than 10° from vertical. Lift the cabinets only with a forklift or damage may occur. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 64
Remove the three bolts securing the right side shipping bracket to the cabinet and three bolts securing the bracket to the pallet (see Figure 4‐2 or Figure 4‐4). Remove the right side shipping bracket. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Front Door Pallet Shipping Bracket Bolts Shipping Bracket Left Side Shipping Bolts Bracket Figure 4‐1. Removing the ISBM Section Left Side Shipping Bracket P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Carefully lower the cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the remaining cabinet. Proceed to paragraph 4.3. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Retain the hardware for later use. Remove the screws securing the corner channel and remove the channel (see Figure 4‐5). Retain the hardware for later use. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
ISBM section right side is against the UPM section left side and the front of the cabinet bases are flush with each other (see Figure 4‐6). P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
ISBM and UPM sections. Secure the bracket with the screws from the hardware kit (see Figure 4‐7). 13. Proceed to paragraph 4.4. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
ISBM section to the AC Input to UPMs terminals. See Figure 4‐8 for terminal locations. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 72
ISBM section. 14. Connect the ground braid to the ISBM section ground bolt and secure. 4-10 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 73
27. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7; otherwise, proceed to paragraph 4.8. 4-11 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE On a UPS configured as an Input Output Module (IOM), CB4 is not installed. Figure 4‐8. ISBM Section Intercabinet Power Terminal Locations 4-12 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE On a UPS configured as an IOM, UPM input wiring terminations are the same as an ISBM configuration. Figure 4‐9. ISBM Section Input Power Terminal Detail 4-13 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPS SYSTEM INSTALLATION Field Installed UPM Installation NOTE FI-UPM installation is not applicable to a three UPM model. If installing a four UPM model, install the FI-UPM using the instructions in the Eaton ® Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Manual ®...
ISBM section. Install the conduit plate and install all conduit runs into the plate. Pull wiring through conduit into the ISBM section wiring area. 4-18 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
A, B, and C bypass input power wiring from the utility source to the bypass input terminals in the ISBM section. See paragraph 3.2.3 for wiring and termination requirements. 4-20 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
ISBM NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐17. ISBM Section Power Terminal Locations 4-21 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Section A–A NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐18. ISBM Section Power Terminal Detail AA 4-22 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
4.8.1, Step 2. Secure with the retained hardware. Reinstall the left front panel removed in paragraph 4.8.1, Step 1 and secure with the retained hardware. 4-23 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
DC Input from Battery + (E4) Front DC Input from Battery – (E5) Section B–B Figure 4‐19. ISBM Section Power Terminal Detail BB – Common Battery 4-24 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
A V E R T I S S E M E N T ! Des tensions dangereuses sont présentes près de l’enceinte du terminal de l’interface utilisateur si l’onduleur n’est pas totalement débranché. 4-25 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
10. Reinstall the top internal safety shield panel and secure with the retained hardware. 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 4-26 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
(See Figure 4‐22 for detail.) (See Figure 4‐24 for terminal assignments.) For 4-wire systems only ISBM Figure 4‐21. ISBM Section Interface Terminal Locations 4-27 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 90
Building Alarm 5 Return NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. 4-28 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG Figure 4‐23. Typical Alarm Relay Connection 4-29 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4‐24. Terminal Blocks TB1, TB2, and TB3 Connector Assignments 4-30 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Reinstall the interface entry plate and install the conduit. NOTE The Eaton 9395P-1200 system can trip a maximum of six battery cabinets total. This applies to both the 1085 standard and High Rate series batteries. If more than six battery cabinets in total are needed in a separate UPM battery configuration, DO NOT hook up the shunt trips.
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. Figure 4‐26. Typical Battery Interface Connection – Separate Battery System 4-32 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Refer to the manual supplied with the X-Slot card for operator instructions. X-Slot Communication Bay 1 X-Slot Communication Bay 2 X-Slot Communication Bay 3 X-Slot Communication Bay 4 Figure 4‐27. X-Slot Communication Bays 4-33 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE The REPO switch must be a normally-open or normally-closed latching‐type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
NEC Article 725 Class 2 requirements. 13. Reinstall the top internal safety shield panel and secure with the retained hardware. 4-35 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4‐31. Normally‐Closed and Normally‐Open REPO Switch Wiring 4-36 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 100
- Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) - The debris shields covering the UPS cabinet ventilation grills are removed. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4-38 P-164000500 Rev 4 www.eaton.com/powerquality...
Powerware Hot Sync Can Bridge card (see paragraph 5.1) Parallel system wiring (see paragraph 5.2) RMP II (see paragraph 5.3) RIM II (see paragraph 5.4) SCM II (see paragraph 5.5) P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
X-Slot communication bay locations. To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge Card, see Figure 5‐2 and Table 5‐1. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Normally‐open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN input for parallel operation. Shield P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the top internal safety shield panel and secure with the retained hardware.
NOTE Use twisted pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 108
MOB 2 Aux 2 Com MOB 3 Aux 2 Com Pull Chain MOB Common MOB 3 Aux 2 Com MOB 4 Aux 2 Com P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 5‐8, and Table 5‐5 for the terminal location and wiring information. Close the front door and secure the latch. 10. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. To check the operation of the RMP II, ensure that the UPS is supplying the load via inverter or bypass.
10. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment.
Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐12. Remote Monitor Panel II Dimensions 5-15 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐13. Relay Interface Module II Dimensions 5-16 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐14. Supervisory Contact Module II Dimensions 5-17 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 118
INSTALLING OPTIONS AND ACCESSORIES This page intentionally left blank. 5-18 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 119
Section II Operation 5-19 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 120
5-20 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The backfeed protection contactor is located in series with the static switch. The static switch is armed and ready during normal operation. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
DC converter, depending on the system voltage and the size of the battery string attached to the unit. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPMs take on the increased load. The VMMS redundancy setting sets the number of redundant UPMs that the customer requires. Both the VMMS UPM load limit and UPM redundancy are customer configurable. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The backfeed protection contactor is normally closed, ready to support the static switch unless the bypass input source becomes unavailable. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
K1 and K5 prevent system voltages from bleeding backwards through the static switch and rectifier snubber components and re-entering the input source. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present. Figure 6‐4. Path of Current Through the UPS in Battery Mode P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
, and map to Table 3‐5 on page 3-13. Figure 6‐9. UPS System – Four UPM Common Rectifier Feed, Common Battery, IOM Configuration 6-13 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
, and map to Table 3-5 on page 3-13. Figure 6‐10. UPS System – Four UPM Common Rectifier Feed, Separate Battery, IOM Configuration 6-14 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
(BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6‐11. Simplified Dual-Feed UPS with Maintenance Bypass Panel 6-15 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPM to be in double-conversion mode at all times; otherwise, Variable Module Management mode operates the same as it does in a single UPS system (see paragraph 6.2.4). 6-16 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Bypass mode. The distributed bypass system automatically returns to Normal mode when the overload condition is cleared and system operation is restored within specified limits. 6-17 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
If more modules than can support the load must be taken offline, the load must be transferred to maintenance bypass or shut down. 6-18 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
In the Parallel Capacity (N+0) arrangement, if one UPS trips offline and goes to bypass, the remaining UPSs also go to bypass. 6-19 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Output to Main Power Flow Critical Load Open Figure 6‐14. Path of Current through the UPSs in Battery Mode – Distributed Bypass 6-20 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 7.3. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPS. For a description of the control panel functions, see paragraph 7.3. Color Touchscreen Control Panel ISBM Figure 7‐2. Color Touchscreen Control Panel Location (Typical) P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
When the unit powers up, the screen displays as shown in Figure 7‐3. When power is applied to the system, the display advances to the Sign In screen shown in Figure 7‐4 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
(see Figure 7‐5). Figure 7‐4. Parts of the Touch Screen P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol between the system model and time allows the operator select a different language from an imbedded list.
NOTE Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 7‐7. Main Menu and Power Maps Screen (Online Mode) Touching the LOAD kVA button displays the Output kVA screen shown in Figure 7‐8 Figure 7‐8. Output kVA Screen from Home Screen P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 7‐9. Average Efficiency Screen from Home Screen Touching the CONSUMPTION button displays the screen shown in Figure 7‐10. Figure 7‐10. Consumption Screen from Home Screen P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 7‐12 is an example of a command request confirmation pop-up screen. This type of pop-up allows the user to confirm that the requested command is valid. Figure 7‐12. Typical Command Confirmation Screen (Charger Off) P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
24 hours, 7 days, 30 days, or 1 year. This is true of all the meters screens listed in the top section. Figure 7‐9 Figure 7‐10 Figure 7‐13. Meters Summary Screen 7-10 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The Select Source screen shown in Figure 7‐18 allows the operator to choose the individual source for system readings. Figure 7‐18. Select Source Screen 7-13 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
LCD in the UPS status area. This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. 7-16 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Selecting an event opens the Event Detail screen shown in Figure 7‐25. This screen details the specifics of the event for the user to see. Figure 7‐25. User Log Detail Screen 7-17 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 7‐27 shows the Module Controls screen. This screen allows control of the individual modules within the system. It also gives their values and status. Figure 7‐27. Module Controls Screen 7-18 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation. Figure 7‐31. Settings Screen 7-20 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The various Energy Advantage Architecture operations are described in the UPS Installation and Operation manual for your system. Figure 7‐33. Energy Advantage Architecture (EAA) Screen 7-21 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 7‐35. High Alert Timer Screen This screen shown in Figure 7‐35 asks the operator if they want to start the High Alert mode timer. 7-22 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
The screen shown in Figure 7‐36 allows the operator to query the system for various operational statistics such as shown in Figure 7‐37. Figure 7‐36. Statistics Basic Screen Figure 7‐37. Statistics Data Detail Screen 7-23 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
7.3.20 System Overview Screen The screen shown Figure 7‐40 displays values for all UPS and UPM parameters. Figure 7‐40. System Overview Screen 7-25 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Online mode. 7-26 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
L’alimentation de la charge critique est complètement coupée lorsque le circuit d’arrêt d’urgence à distance est déclenché à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension. 7-27 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPS OPERATING INSTRUCTIONS NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch. To use the REPO switch: Firmly push the red pushbutton until it locks into place.
A monthly summary report that delivers key performance information, alarms and trended health data about your Eaton 9395P-1200 UPS, based on the prior month’s data. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Protector, which allows graceful shutdown of operating systems. Eaton’s Intelligent Power Software gives you all the tools you need to monitor and manage power devices on your network, even in a virtualized environment. This innovative software solution combines the most critical applications in ensuring system up-time and data integrity: not only power monitoring and management, but also graceful shutdown during an extended power outage.
Contacts should not be operated in excess of 30 Vac @ 5A maximum. MISE EN GARDE! Ne pas faire fonctionner les contacts à plus de 30 VCA à 5 A maximum. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Figure 8‐2 shows an RMP II. Figure 8‐2. Remote Monitor Panel II P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 178
The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
TB2‐10 through TB2‐12 ON BATTERY TB2‐13 through TB2‐15 UPS ALARM TB2‐16 through TB2‐18 ON BYPASS TB2‐19 through TB2‐21 SHUTDOWN IMMINENT TB2‐22 through TB2‐24 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such grounds are removed during installation and maintenance. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
0.25” UPM Section Air Filters 20” 44” 0.25” C A U T I O N Verify washed filters are thoroughly dry before reinstalling. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 183
Reinstall the ISBM section front panel removed in Step b and secure with the retained hardware. h. If opened, close the front door and secure the latch. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
ISBM Air Filters Bottom Right ISBM Air Filters For 4-wire systems only Figure 9‐1. ISBM Section Air Filter Locations – Continuous Static Switch P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
If the UPS is a four UPM model, check the Field Installed UPM (FI-UPM) air filter (located behind the front panel) and wash or replace as necessary. See Figure 9‐3 for the filter location. The FI-UPM filter size is 20” 44” 0.25”. Contact an Eaton service representative for a replacement filter. To remove the filter:...
9.2.5 BATTERY Maintenance Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized service personnel. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Ne pas éliminer les déchets d’équipements électriques et électroniques (DEEE) aux ordures. Pour connaître la méthode d’élimination appropriée, communiquer avec le centre régional de récupération/réutilisation ou d’élimination des déchets dangereux. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Eaton Help Desk (see page 1-10). P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
3% THD at full load Power Factor Minimum 0.99 at full load Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4 10-1 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
125% for 120 seconds 150% for 15 seconds NOTE The 125% and 150% overloads are based on the non-derated hardware capability of the UPS. 10-2 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse Immunity without damage and with no disturbance or adverse effect to the critical load. 10-3 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 192
PRODUCT SPECIFICATIONS This page intentionally left blank. 10-4 P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...
Page 193
Eaton-built battery cabinets, (individually and collectively, the “Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts and labor, as applicable), at the option of Eaton.
Page 194
WARRANTY This page intentionally left blank. P-164000500 Rev 4 www.eaton.com/powerquality Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual...