Eaton Power Xpert 9395P-1100/1100 Installation And Operation Manual page 55

Table of Contents

Advertisement

Table 15. 380V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Separate
Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect to Each
UPS UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
NOTE Callout letters A, B, C, and D map to
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly, however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly
(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the
return current path and cause a loss of all phase-to-neutral loads.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
Terminals E1A through E5A and E9A through E11A are stud type terminals. The intercabinet power wiring
connections for this equipment are rated at 90°C. See
Table 17
for supplied intercabinet wiring terminal hardware.
The torque values listed in
Table 16
breaking or twisting the stud.
Figure 24
through
Figure 27
Units
kVA
kW
Volts
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps per UPM
C
AWG or kcmil
(each)
Total Amps
D
AWG or kcmil
(each)
Figure
66.
Table 16
for the M8 studs are the maximum allowable. Tightening further will risk
show the location of the intercabinet power cable terminals inside the UPS.
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
UPS Installation Plan and Unpacking
Rating 50/60 Hz
675
750
825
675
750
825
380/380 380/380 380/380 380/380 380/380 380/380
1200
1363
1500
1600
500
500
500
(5)
(6)
(6)
1026
1139
1253
1367
500
500
500
(5)
(5)
(5)
603
603
603
500
500
500
(3)
(3)
(3)
1026
1139
1253
1367
500
500
500
(5)
(5)
(5)
for intercabinet power cable terminations and
900
1000
1100
900
1000
1100
1818
2000
500
500
500
(6)
(8)
(8)
1519
1671
500
500
500
(6)
(6)
(8)
603
603
603
500
500
500
(3)
(3)
(3)
1519
1671
500
500
500
(6)
(6)
(8)
37