1 1 0 0 . . 2 2 . . 3 3 U U P P S S E E n n v v i i r r o o n n m m e e n n t t a a l l
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (Operating and Storage)
Acoustical Noise
EMI Emissions and Immunity
Electrostatic Discharge (ESD) Immunity
All ratings except 1200 kW, 900 kW:0 to 40°C (32 to 104°F) without
derating.
For 1200 kW, 900 kW:0 to 35°C at elevation up to 1000m without
derating.
The recommended operating temperature is 25°C (77°F).
Maximum 1000m (3300 ft) at 40°C without derating
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self discharge)
5% to 95% maximum non-condensing
78 dB at a 1m distance, A weighted for one UPM UPS
81 dB at a 1m distance, A weighted for two UPM UPS
Meets FCC Regulation 47, Part 15, for class A devices
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.