C C h h a a p p t t e e r r 1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s
1 1 0 0 . . 1 1 M M o o d d e e l l N N u u m m b b e e r r s s
The UPS is housed in two or three free-standing cabinets with safety shields behind the door and front panels.
The UPS is available in 50 or 60 Hz with various output power ratings.
Models
Eaton 9395P-1200/1200* (four UPM)
Eaton 9395P-1200/1200 (four UPM)
Eaton 9395P-1200/1100 (four UPM)
Eaton 9395P-1200/1000 (four UPM)
Eaton 9395P-1200/900 (three UPM)
Eaton 9395P-1200/900 (four UPM)
Eaton 9395P-1200/825 (three UPM)
Eaton 9395P-1200/750 (three UPM)
Eaton 9395P-1200/675 (three UPM)
1 1 0 0 . . 2 2 S S p p e e c c i i f f i i c c a a t t i i o o n n s s
The following sections detail the input, output, environmental, and battery specifications for the UPS.
1 1 0 0 . . 2 2 . . 1 1 U U P P S S I I n n p p u u t t
Operating Input Voltage
Operating Input Frequency Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Power Rating
1200 kVA,
1200 kW
1200 kVA,
1200 kW
1100 kVA,
1100 kW
1000 kVA,
1000 kW
900 kVA,
900 kW
900 kVA,
900 kW
825 kVA,
825 kW
750 kVA,
750 kW
675 kVA,
675 kW
480 Vac
50/60 Hz
See
Table 6
or
See
Table 8
or
See
Table 10
or
See
Table 12
or
See
Table 14
or
Reduced for Generator
Adjustable
3% THD at full load
Minimum 0.99 at full load
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
Table 7
for 480V four UPM models.
Table 9
for 480V three UPM models.
Table 11
for 415V three/four UPM models.
Table 13
for 400V three/four UPM models.
Table 15
for 380V three/four UPM models.
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz