Table 11. 415V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Separate
Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect to Each
UPS UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
NOTE Callout letters A, B, C, and D map to
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly, however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly
(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the
return current path and cause a loss of all phase-to-neutral loads.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
Units
kVA
kW
Volts
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps per UPM
C
AWG or kcmil
(each)
Total Amps
D
AWG or kcmil
(each)
Figure
68.
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
UPS Installation Plan and Unpacking
Rating 50/60 Hz
675
750
825
675
750
825
415/415 415/415 415/415 415/415 415/415 415/415
1156
1284
1412
1541
500
500
500
(5)
(6)
(6)
939
1043
1148
1252
500
500
500
(4)
(5)
(5)
603
603
603
500
500
500
(3)
(3)
(3)
939
1043
1148
1252
500
500
500
(4)
(5)
(5)
900
1000
1100
900
1000
1100
1712
1883
500
500
500
(6)
(8)
(8)
1391
1530
500
500
500
(5)
(6)
(6)
603
603
603
500
500
500
(3)
(3)
(3)
1391
1530
500
500
500
(5)
(6)
(6)
33