UPS Operating Instructions
7 7 . . 3 3 . . 1 1 S S t t a a t t u u s s I I n n d d i i c c a a t t o o r r s s
The symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED)
lamps work with the alarm horn to let you know the operating status of the UPS. See
Table 35. Status Indicators
Indicator
Green
Yellow
Yellow
Red
140
Eaton
®
Status
Description
Lit Steady
The UPS is in Online mode, operating normally. The power module is supplying power to
the critical load.
Lit Steady
The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the
Normal indicator also remains illuminated.
Lit Steady
The UPS is in Bypass mode. The critical load is supported by the bypass source. The
Online indicator is not illuminated when the system is in Bypass mode.
Lit Steady
The UPS has an active alarm and requires immediate attention. The screen shows the
highest priority active alarms. All alarms are accompanied by an audible horn. To silence
the horn, press any control panel pushbutton once. The Alarm indicator may be
illuminated along with other indicators.
Lit Flashing
There is a new UPS alarm condition. The indicator flashes until acknowledged by
pressing any control panel pushbutton once.
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11