Eaton Power Xpert 9395P-1100/1100 Installation And Operation Manual page 49

Table of Contents

Advertisement

Table 9. 480V Input/Output Ratings and External Wiring Requirements for the Three UPM – Separate Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect to Each UPS
UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
NOTE Callout letters A, B, C, and D map to
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly, however it is important to evaluate whether the critical load will function properly as its neutral reference is
rapidly (50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will
interrupt the return current path and cause a loss of all phase-to-neutral loads.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
Units
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps per UPM
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
Figure
69.
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
UPS Installation Plan and Unpacking
Rating 50/60 Hz
kVA
675
750
675
750
kW
Volts
480/480 480/480 480/480 480/480
1002
1113
500
500
(6)
(6)
812
902
500
500
(5)
(5)
658
658
500
500
(3)
(3)
812
902
500
500
(5)
(5)
825
900
900
825
825
900
480/480
1225
1225
1336
500
500
500
(6)
(6)
(6)
992
1083
1083
500
500
500
(5)
(5)
(5)
658
658
658
500
500
500
(3)
(3)
(3)
992
1083
1083
500
500
500
(5)
(5)
(5)
31