UPS Installation Plan and Unpacking
Table 14. 380V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Common
Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
NOTE Callout letters A, B, C, and D map to
NOTE Bypass wiring data is not applicable to IOM configurations.
Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for
optimum system performance and battery run time.
Battery Cable Routing Requirements
Conduit applications:
* Each conduit must have a Positive, Negative, and Ground conductor.
* There must be an equal number of positive and negative conductors in a single conduit. Only one ground conductor is required in
each conduit.
Raceway applications:
* Positive and negative battery cables must be run side by side in the raceway in an alternating pattern (+ - + - + - + -).
* There must be a ground cable running in the raceway with the battery cables.
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly, however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly
(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the
return current path and cause a loss of all phase-to-neutral loads.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
36
Eaton
®
Figure
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
Units
kVA
675
kW
675
Volts
380/380 380/380 380/380 380/380 380/380 380/380
Amps
1200
A
AWG or kcmil
500
(each)
(5)
Amps
1026
B
AWG or kcmil
500
(each)
(5)
Amps
1480
C
AWG or kcmil
500
(each)
(6)
Amps
1026
D
AWG or kcmil
500
(each)
(5)
66.
Rating 50/60 Hz
750
825
900
1000
750
825
900
1000
1363
1500
1600
1818
500
500
500
500
(6)
(6)
(6)
(8)
1139
1253
1367
1519
500
500
500
500
(5)
(5)
(6)
(6)
1645
1809
1974
2193
500
500
500
500
(8)
(8)
(8)
(9)
1139
1253
1367
1519
500
500
500
500
(5)
(5)
(6)
(6)
1100
1100
2000
500
(8)
1671
500
(8)
2412
500
(12)
1671
500
(8)