Figure 124. Isbm Section Air Filter Locations - Continuous Static Switch - Eaton Power Xpert 9395P-1100/1100 Installation And Operation Manual

Table of Contents

Advertisement

b.
Remove one top screw and two bottom screws securing the ISBM left front panel (see
the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
c.
If the UPS is a continuous static switch configuration, unfasten the front door latch and swing the door
open (see
d.
Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from
the cabinet.
e.
Push the washed or new foam filters over the screw heads on the cabinet mounted studs until seated
against the cabinet.
f.
Reinstall the UPM section front panels removed in Step a and secure with the retained hardware.
g.
Reinstall the ISBM section front panel removed in Step b and secure with the retained hardware.
h.
If opened, close the front door and secure the latch.
Figure 124. ISBM Section Air Filter Locations – Continuous Static Switch
Bottom Left
ISBM Air Filters
Figure
17).
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
UPS Maintenance
Figure
18). Lift
Middle Right
ISBM Air Filter
Bottom Right
ISBM Air Filters
For 4-wire
systems only
187