UPS System Installation
5.
Locate the 1G1, 1G2, 2G1, 2G2, 3G1, and 3G2 power wiring harnesses. Route these harnesses through
the wiring access in the right side panel of the ISBM section to the AC Input to UPMs terminals. See
Figure 24
NOTE
6.
Locate the intercabinet wiring terminal hardware kit packed on the bottom right side of the ISBM section.
7.
Using hardware from the intercabinet wiring terminal hardware kit (see
C cable lug connections to the AC Input to UPMs terminals. Follow the callout details in
connect the correct cable lug to the proper terminals. See paragraph
3.2.4 UPS System Power Wiring Preparation
8.
Locate the 1G3, 2G3, and 3G3 power wiring harnesses. Route these harnesses through the wiring access
in the right side panel of the ISBM section to the DC Input to UPMs terminals. See
locations.
NOTE
9.
Using hardware from the intercabinet wiring terminal hardware kit (see
negative cable lug connections to the DC Input to UPMs terminals. Follow the callout details in
to connect the correct cable lug to the proper terminals. See paragraph
3.2.4 UPS System Power Wiring Preparation
NOTE
10. Locate the 1G4, 1G5, 2G4, 2G5, 3G4, and 3G5 power wiring harnesses. Remove the front two columns of
wire ties securing the cables to facilitate routing cables to the AC Output from UPMs terminals. See
Figure 24
NOTE
11. Using hardware from the intercabinet wiring terminal hardware kit (see
C cable lug connections to the AC Output from UPMs terminals. Follow the callout details in
connect the correct cable lug to the proper terminals. See paragraph
3.2.4 UPS System Power Wiring Preparation
12. Install the remaining hardware (three washers, conical washers, and nuts) onto the AC Input to UPMs
terminals designated for the four UPM model and secure the hardware (see ). This hardware is used by an
Eaton Customer Service Engineer to install a Field Installed UPM (FI-UPM).
13. Locate the ground braid in the bottom left front corner of the UPM section. The ground braid is secured at
the factory to the UPM section ground bolt. Route the ground braid through the wiring access in the right
side panel of the ISBM section to the ground bolt in the ISBM section.
14. Connect the ground braid to the ISBM section ground bolt and secure.
NOTE
60
Eaton
®
for terminal locations.
Two cable lugs will be connected to each terminal stud. When connecting the cable
lugs, install the first lug on the stud with the raised barrel portion facing the back of the
cabinet. Install the second lug with the raised barrel portion facing the front of the
cabinet.
When connecting the UPM battery cables, verify the cables are connected to the correct
terminals.
AC output intercabinet power wiring harnesses are supplied attached to the interior left
side panel of the UPM section (see
for terminal locations.
Two cable lugs will be connected to each terminal stud. When connecting the cable
lugs, install the first lug on the stud with the raised barrel portion facing the back of the
cabinet. Install the second lug with the raised barrel portion facing the front of the
cabinet.
Four intercabinet interface wiring harnesses are supplied coiled inside the protective
cage on the right side panel of the ISBM section (see A in
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
Table
for wiring and termination requirements.
Table
for wiring and termination requirements.
Figure
21).
Table
for wiring and termination requirements.
17), connect phase A, B, and
Figure 25
to
Figure 24
for terminal
17), connect the positive and
Figure 26
17), connect phase A, B, and
Figure 27
Figure
28).
to