Eaton Power Xpert 9395P-1100/1100 Installation And Operation Manual page 22

Table of Contents

Advertisement

Introduction
Alarm Contact – One alarm contact is provided for connection to equipment at the facility, such as a light,
an audible alarm, or a computer terminal. The equipment connected to this contact alerts you to a UPS
alarm. See
X-Slot Communication Bays – Four communication bays are standard equipment. One to four optional X-
Slot
®
connectivity cards can be installed in the UPS module at any time. X-Slot cards are quickly installed at
the front of the UPS and are hot-pluggable. See
1 1 . . 2 2 . . 4 4 A A d d v v a a n n c c e e d d B B a a t t t t e e r r y y M M a a n n a a g g e e m m e e n n t t
A three-stage charging system increases battery service life by optimizing recharge time, and protects batteries
from damage due to high current charging and inverter ripple currents. Charging at high currents can overheat
and damage batteries.
1 1 . . 2 2 . . 5 5 P P o o w w e e r r M M a a n n a a g g e e m m e e n n t t S S o o f f t t w w a a r r e e
Eaton's Intelligent Power
Intelligent Power
allows graceful shutdown of operating systems. See
1 1 . . 3 3
O O p p t t i i o o n n s s a a n n d d A A c c c c e e s s s s o o r r i i e e s s
Contact an Eaton sales representative for information about the following options.
1 1 . . 3 3 . . 1 1 I I n n t t e e g g r r a a t t e e d d B B a a t t t t e e r r y y C C a a b b i i n n e e t t s s
Battery backup protection can be provided by equipping the UPS system with Eaton 9395P-1200 battery
cabinets containing sealed lead-acid, maintenance-free batteries. The cabinets are designed for standalone
installation and may be installed adjacent to the UPS or in a separate location. The recommended installation
location for adjacent battery cabinets is on the right side of the UPS cabinet to allow for future expansion using
an external module.
Consult the Eaton
Installation Manual (P-164000580) for specifics on battery cabinet usage with the 9395P-1200.
1 1 . . 3 3 . . 2 2 F F i i e e l l d d I I n n s s t t a a l l l l e e d d U U P P M M
A Field Installed UPM (FI-UPM) provides upgradability for the Eaton 9395P-1200 Three UPM UPS. The FI-UPM
may be installed at any time in the future when power needs change. The module cabinet is installed on the
left side of the ISBM section and is wired directly to the UPS. No input or output wiring changes are needed for
a capacity increase if the original installation was wired for increased capacity. Operation remains the same as
the original UPS.
1 1 . . 3 3 . . 3 3 S S y y n n c c C C o o n n t t r r o o l l
An optional Eaton
9395P-1200 UPS systems in synchronization. This option facilitates the uninterrupted transfer of the load from
one load bus to another by means of transfer switches. The Sync Control is housed in a wall-mounted panel
that can be located between the UPS units for easy wiring.
1 1 . . 3 3 . . 4 4 S S i i n n g g l l e e - - F F e e e e d d K K i i t t
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a single-feed configuration.
The kit consists of jumpers and bus bar extensions for each phase, and the hardware required for installation.
1 1 . . 3 3 . . 5 5 D D i i s s t t r r i i b b u u t t e e d d B B y y p p a a s s s s S S y y s s t t e e m m
There are two types of redundancy: UPS based (based on the number of UPSs) and UPM based (based on the
number of UPMs). Each UPS contains two to three UPMs.
A distributed bypass UPS system with two to five UPSs can be installed to provide a capacity and/or redundant
system. This load sharing system provides more capacity than a single UPS, and can provide backup,
4
Eaton
®
Chapter 8 Communication
®
Software solution, based on Web2.0 technology, includes two applications:
®
Manager
for UPS management and monitoring, and Intelligent Power
®
Power Xpert
®
9395/9395P Integrated Battery Cabinet (Models 1085 and 1085HR)
®
9395P-1200 Sync Control maintains the critical load outputs of two separate single module
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
for additional information.
Chapter 8 Communication
Chapter 8 Communication
for additional information.
®
Protector
, which
for additional information.