Installing Options and Accessories
4.
Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see
5.
Reinstall the conduit landing plate.
6.
Install conduit between the UPS and RMP II. See
7.
Install wiring between the UPS and RMP II. See
Bridge Card terminal location and wiring information, and
terminal location and wiring information.
NOTE
8.
Install 120 Vac power wiring from the critical bus to the RMP II. See
the terminal location and wiring information.
9.
Close the front door and secure the latch.
10. Restart the UPS. See

Figure 54. Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations

Terminal TB1
Signal Connections
from the UPS
104
Eaton
®
120 Vac for the RMP II should be supplied from the critical bus by facility planners or the
customer.
Chapter 7 UPS Operating Instructions
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
Figure 59
for RMP II knockout hole location.
Figure 49
and
Table 29
for the Powerware Hot Sync CAN
Figure
54,
Figure
Figure
for startup instructions.
Ground
Terminal
Terminal TB3
120 Vac Power
Figure
55, and
Table 33
for the RMP II
54,
Figure
55, and
Table 33
32).
for