Table 5. 415V/400V/380V Air Conditioning and Ventilation Requirements During Full Load Operation
Model
Eaton 9395P-1100/1100
(CSS)
Eaton 9395P-1000/1000
(CSS)
Eaton 9395P-1200/900
(CSS)
Eaton 9395P-1200/825
(CSS)
Eaton 9395P-1200/750
(CSS)
Eaton 9395P-1200/675
(CSS)
NOTE CSS = Continuous Static Switch.
Input/
Output
Heat Rejection BTU/hr
Rating
Voltage
415/414
1100 kVA
400/400
1100 kVA
380/380
415/414
1000 kVA
400/400
1000 kVA
380/380
415/414
900 kVA
400/400
900 kVA
380/380
415/414
825 kVA
400/400
825 kVA
380/380
415/414
750 kVA
400/400
750 kVA
380/380
415/414
675 kVA
400/400
675 kVA
380/380
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
UPS Installation Plan and Unpacking
x1000 (kg-cal/hr)
50.2 (172)
44.1 (151)
38.2 (131)
37.7 (129)
33.1 (113)
28.7 (98)
Ventilation Required for
Cooling Air Exhaust
Approximately 3300 liter/sec
(7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec
(9000 CFM)
Approximately 2400 liter/sec
(5000 CFM)