ABB RELION 670 Series Technical Manual page 161

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
IAn
ANSI07000018 V3 EN-US
Figure 52: Internal fault
IAn
IAt
ANSI07000019 V2 EN-US
Figure 53: External fault
Generator differential protection GENPDIF (87G) function uses two mutually independent
characteristics to which magnitudes of the three fundamental frequency RMS differential currents
are compared at each execution of the differential protection function. These two characteristics
divide, each of them independently, the operate current – restrain current plane into two regions:
the operate (trip) region and the restrain (block) region, as shown in figure 55. Two kinds of
protection are obtained:
the non-stabilized (instantaneous unrestrained) differential protection
the stabilized differential protection
The non-stabilized (instantaneous) differential protection is used for very high differential
currents, where it must be beyond any doubt, that the fault is internal. This limit, (defined by the
Technical manual
IAn
External fault: IAn = - IAt
Idiff = 0
IAt
IAt
Idiff
ANSI0700018_3_en.vsd
IAt
IAn
en07000019-2_ansi.vsd
Section 6
Differential protection
155