ABB RELION 670 Series Technical Manual page 102

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 5
Local Human-Machine-Interface LHMI
Automatic reset
Operating sequence
The sequences can be of type Follow or Latched. For the Follow type, the LED follows the input
signal completely. For the Latched type, each LED latches to the corresponding input signal until it
is reset.
The figures below show the function of available sequences selectable for each LED separately.
The following 6 sequences are available:
Sequence 1: Follow-S
Sequence 2: Follow-F
Sequence 3: LatchedAck-F-S
Sequence 4: LatchedAck-S-F
Sequence 5: LatchedColl-S
Sequence 6: LatchedReset-S
sequence 1 and 2 , which are of the Follow type, the acknowledgment (Ack ) /reset function is
For
not applicable because the indication shown by the LED follows its input signal.
which are of the Latched type with acknowledgement, are only working in collecting (Coll) mode.
Sequence 5 is working according to Latched type and collecting mode while Sequence 6 is working
according to Latched type and re-starting (Reset) mode. The letters
names have the meaning
At the activation of the input signal to any LED, the indication on the corresponding LED obtains a
color that corresponds to the activated input, and operates according to the selected sequence
diagrams shown below.
In the sequence diagrams the different statuses of the LEDs are shown using the following
symbols:
= No indication
= Green
G
IEC09000311 V1 EN-US
Figure 16: Symbols used in the sequence diagrams
Sequence 1 (Follow-S)
This sequence follows the corresponding input signals all the time with a steady light. It does not
react on acknowledgment or reset. Every LED is independent of the other LEDs in its operation.
96
operated from an external push button or a function button. The function is positive
edge triggered, not level triggered. This means that even if the button is continuously
pressed, the acknowledgment/reset only affects indications active at the moment when
the button is first pressed.
The automatic reset can only be performed for LED indications defined for re-starting
mode with the latched sequence type 6 (LatchedReset-S). When the automatic reset of
the LEDs has been performed, still persisting indications will be indicated with a steady
light.
S = Steady and F = Flash.
= Steady light
= Yellow
Y
S and F in the sequence
= Flash
= Red
R
IEC09000311.vsd
1MRK 502 066-UUS B
GUID-DFCA880B-308C-4334-94DF-97C7765E8C13 v5
Sequence 3 and 4 ,
SEMOD56072-39 v4
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670

Table of Contents