ABB RELION 670 Series Technical Manual page 119

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Name
Values (Range)
NegSeqDiffEn
Disabled
Enabled
IMinNegSeq
0.02 - 0.20
NegSeqROA
30.0 - 120.0
Table 50: T2WPDIF (87T) Group settings (advanced)
Name
Values (Range)
EndSection1
0.20 - 1.50
EndSection2
1.00 - 10.00
SlopeSection2
10.0 - 50.0
SlopeSection3
30.0 - 100.0
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
OpenCTEnable
Disabled
Enabled
tOCTAlarmDelay
0.100 - 10.000
tOCTResetDelay
0.100 - 10.000
tOCTUnrstDelay
0.10 - 6000.00
Table 51:
T2WPDIF (87T) Non group settings (basic)
Name
Values (Range)
GlobalBaseSelW1
1 - 12
GlobalBaseSelW2
1 - 12
ConnectTypeW1
WYE (Y)
Delta (D)
ConnectTypeW2
WYE (Y)
Delta (D)
Table continues on next page
Technical manual
Unit
Step
Default
-
-
Enabled
IB
0.01
0.04
Deg
0.1
60.0
Unit
Step
Default
IB
0.01
1.25
IB
0.01
3.00
%
0.1
40.0
%
0.1
80.0
%
0.1
15.0
%
0.1
25.0
-
-
Disabled
s
0.001
3.000
s
0.001
0.250
s
0.01
10.00
Unit
Step
Default
-
1
1
-
1
1
-
-
WYE (Y)
-
-
WYE (Y)
Differential protection
Description
Operation Off/On for neg. seq. differential
protections
Negative sequence current must be higher
than this level to be used
Operate Angle for internal / external
negative sequence fault discriminator
Description
End of section 1, multiple of Winding 1
rated current
End of section 2, multiple of Winding 1
rated current
Slope in section 2 of operate-restrain
characteristic, in %
Slope in section 3 of operate-restrain
characteristic, in %
Max. ratio of second harmonic to
fundamental harm dif. curr. in %
Max. ratio of fifth harmonic to
fundamental harm dif. curr. in %
Open CT detection feature. Open CTEnable
Off/On
Open CT: time in s to alarm after an open
CT is detected
Reset delay in s. After delay, diff. function
is activated
Unrestrained diff. protection blocked after
this delay, in s
Description
Global base selector for winding 1
Global base selector for winding 2
Connection type of winding 1: Y-wye or D-
delta
Connection type of winding 2: Y-wye or D-
delta
Section 6
113