17.29 EIPNDST (EtherNet/IP Node Status Acquisition Instruction)
Operand [S] setting
Specify node numbers in the range of 1 to 256.
Operand [D1] setting
The results of read node statuses are set as follows.
Bits
Name
0
Owned
1
Reserved
2
Configured
3
Reserved
4 to 7
Extended Device Status
8
Minor Recoverable Fault
Minor Unrecoverable
9
Fault
10
Major Recoverable Fault
Major Unrecoverable
11
Fault
12 to 15 Reserved
(Note 1)
For bits 4 to 7, the following field definition contents for "Extended Device Status" are stored. FP7
does not return the codes that are indicated as "Not supported" in the following table.
Bits 4 to 7
0000
0001
0010
0011
0100
0101
0110
0111
WUME-FP7CPUPGR-12
Definition
Turns ON when FP7 is a target and connected from an originator.
It is always 0.
Turns ON when the settings of the EtherNet/IP device are different from
the factory default settings.
It is always 0.
Shows the detailed status of EtherNet/IP device. It is a vendor-specific
status or a status according to CIP.
Stores the error information of the EtherNet/IP device. Error contents vary
depending on vendors.
Recoverable Fault: In a recoverable state
Unrecoverable Fault: In an unrecoverable state
It is always 0.
Name
During self-testing operation or unknown
During the update of firmware
More than one I/O connection is in a fault state
No I/O connection has been established
Setting error of non-volatile memory
Major Fault. The bit 10 or 11 is ON.
More than one I/O connection is established and there is more than one
connection that receives RUN mode.
More than one I/O connection is established and all received connections are
in the Idle mode.
(Note 1)
FP7
Not
suppor
ted
Not
suppor
ted
Not
suppor
ted
Not
suppor
ted
Not
suppor
ted
17-149