17.3

Warning messages

Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Faults, causes and remedies
Warning displayed:
ƒ
The status display is marked in yellow.
ƒ
Warning message, warning code (W...)
Warnings indicate restricted pump function. The pump continues to operate in re-
stricted mode (emergency operation).
Depending on the cause of the warning, emergency operation leads to a restriction
of the control function and even reactivation of a fixed speed.
If the pump identifies as part of permanent monitoring that the cause of the warn-
ing no longer applies, the warning is revoked and operation resumes.
If there is a warning message, the display is permanently on and the green LED indicator
is off.
The following table gives an overview of possible messages in the display:
Universal
Display text
Warning
Warning
Please check operating
Check the installation and operating instructions
manual
Double pump
Twin-head pump
This head
Location: This head
Partner head
Location: Partner head
Exists since:
Since
Acknowledge needed
Confirmation required
For acknowlege long
Press and hold the button for acknowledgement
press knob
Acknowleged, waiting
Acknowledged, waiting for restart
for restart
Reset energy counter
Reset energy counter
Press return key to can-
Press "Back" to cancel
cel
Press and hold return
Press and hold "Back" to cancel
key to cancel
System Notification
System notification
no valid Parameter
No valid parameters
Production mode active
Production mode active
HMI blocked
Display blocked
Code
Warning
550
There is flow through
the pump in the oppos-
ite direction of flow.
Additional information about causes and remedy:
If flow passing through pump in the opposite direction is too strong, the mo-
tor can no longer start.
551
Undervoltage
Additional information about causes and remedy:
The pump is running. Undervoltage reduces the pump's performance.
If the voltage continues to drop, reduced operation cannot be maintained.
552
There is externally gen-
erated flow through the
pump in the direction of
flow.
Additional information about causes and remedy:
The pump can start despite flow.
Cause
Remedy
External influences
Check power control of the
cause flow against
pumps,
the direction of the
install swing check valve if
pump's flow.
needed.
Power supply too low.
Check power supply.
Power supply has
fallen below a min-
imum limit value.
External influences
Check power control of the
cause flow in the
other pumps.
pump's direction of
flow.
en
195