12.5.2
Using the analogue input AI2 as
the setpoint input
Analogue input (AI2)
Signal type
Fig. 74: Analogue input menu (AI2)
Signal type (AI2)
Fig. 75: Signal types menu (AI2)
178
Communication interfaces: Setting and function
Fig. 73: Behaviour of analogue input AI1: Sensor value with signal type 0 ... 10 V / 0 ... 20
mA
The setting of the analogue input AI 2 is only available in the menu if the analogue in-
put AI2 was previously selected in the menu. To do this, select the following in the
menu in succession:
Universal
Display text
1.0
Settings
1.1
Control settings
1.1.9
Setpoint source
1.1.9 / 2
Analogue input (AI2)
The signal type is set via the menu
put AI2".
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.4
Analogue input (AI2)
1.3.4.1
Signal type
Possible signal types when selecting the analogue input as the setpoint input:
Setpoint sensor signal types:
0 ... 10 V: Voltage range from 0 ... 10 V for the transmission of setpoints.
2 ... 10 V: Voltage range from 2 ... 10 V for transmission of setpoints.
0 ... 20 mA: Electric current range from 0 ... 20 mA for the transmission of setpoints.
4 ... 20 mA: electric current range of 4 ... 20 mA for transfer of setpoints.
The analogue input AI2 can only be used as an input for an external setpoint sensor.
Signal type 2 ... 10 V / 4 ... 20 mA:
If an external setpoint sensor is set up at analogue input AI2, the signal type must be
set. In this case 2 ... 10 V or 4 ... 20 mA.
The analogue signal runs between 5 V ... 10 V or between 10 mA ... 20 mA. The ana-
logue signal is interpolated linearly. The applied analogue signal of 5 V or 10 mA repres-
ents the setpoint (for instance the speed) at "0 %". The applied analogue signal of 10 V
or 20 mA represents the setpoint of the differential pressure at "100 %". (See diagram
Fig. 76).
"Settings", "External interfaces", "Analogue in-