Faults, causes and remedies
Code
Warning
553
Electronic module is de-
fective.
Additional information about causes and remedy
The pump is running, but cannot provide full power under the circumstances.
Contact service.
555 /
Implausible sensor value
557
at analogue input AI1 or
AI2.
Additional information about causes and remedy
Incorrect sensor values may lead to substitute operating modes
that ensure functioning of the pump without the required sensor value.
556 /
Cable break at analogue
558
input AI1 or AI2.
Additional information about causes and remedy:
Cable break detection may lead to substitute operating modes that ensure
functioning of the pump without the required external value.
560
Incomplete software
update.
Additional information about causes and remedy:
Software update was not carried out; pump continues to operate with previ-
ous software version.
561 /
Analogue input voltage
562
overloaded (binary or
analogue).
Additional information about causes and remedy:
Binary inputs are impaired. Functions of binary inputs are not available.
1)
564
BMS
setpoint is miss-
ing.
Additional information about causes and remedy:
Control functions impaired. A replacement function is active.
565 /
Signal too strong at
566
analogue input AI1 or
AI2.
Additional information about causes and remedy:
The signal is processed with the maximum value.
570
Electronic module too
hot.
Additional information about causes and remedies:
The electronic module must adjust the pump's operation in the event of no-
ticeable overheating
to prevent damage to electronic components.
571
Twin-head pump con-
nection interrupted.
Additional information about causes and remedy:
Pump function slightly impaired. The motor head meets the pump function
up to the performance limit.
Cause
Remedy
Electronic module is
Replace electronic module.
defective.
The configuration
Check configuration of the
and the present sig-
input and connected
nal lead to an unus-
sensor.
able sensor value.
The configuration
Check configuration of the
and the present sig-
input and connected
nal help identify the
sensor.
cable break.
The software update
Software update with new
was not completed.
software bundle is recom-
mended.
Voltage analogue in-
Check the cables and con-
put short-circuited or
sumers connected to the
too heavily loaded.
analogue input power sup-
ply for short circuits.
Sensor source or
Check configuration and
1)
BMS
is configured
function of BMS
incorrectly.
Communication has
failed.
The available signal is
Check input signal.
significantly over the
expected maximum.
Critical temperature
Ensure permissible ambi-
of the electronic
ent temperature. Improve
module exceeded.
room ventilation.
The connection to
Check power supply of the
the twin-head pump
twin-head pump partner,
partner cannot be
cable connection and con-
made.
figuration.
1)
.
WILO SE 2022-05