Communication interfaces: Setting and function
Set control mode
Δp-c
n-c
PID
Table 29: Application and function of analogue inputs
To change the settings of the analogue inputs, select the following in the menu:
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.3
Analogue input (AI1)
1.3.4
Analogue input (AI2)
The following table gives an overview of the "Analogue input AI1 and AI2" menu:
Universal
Display text
1.3.3
Analogue input (AI1)
1.3.3.1
Signal type
1.3.3.2
Pressure sensor range
1.3.3.3
Pressure sensor position
1.3.3.3 / 1
Pump flange
1.3.3.3 / 2
Standard-compliant position
1.3.4
Analogue input (AI2)
1.3.4.1
Signal type
24 V DC power supply at the analogue input.
NOTICE
The 24 V DC power supply is only available when the analogue input AI1 or AI2 has
been configured for a type of use and a signal type.
The actual value sensor provides the following:
ƒ
Differential pressure sensor values for differential pressure control
ƒ
User-defined sensor values for PID control
When setting the control mode, the type of use of analogue input AI1 as an actual value
input (see Table 28) is automatically preconfigured.
To set the signal type, select the following in the menu:
Function of analogue in-
put AI1
Configured as actual value
input
ƒ
Usage type: Differen-
tial pressure sensor
Configurable:
ƒ
Signal type
ƒ
Sensor measurement
range
ƒ
Sensor position
Not used
Configured as actual value
input
ƒ
Type of use: any
Configurable:
ƒ
Signal type
Function of analogue in-
put AI2
Not configured
Can be used as a setpoint
input
Not configured
Can be used as a setpoint
input
Not configured
Can be used as a setpoint
input