Pump Kick; Ramp Times For Setpoint Change; Automatic Pwm Frequency Reduction - Wilo Yonos GIGA2.0-I Installation And Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

en
14.1

Pump kick

Pump kick
Pump kick: ON/OFF
Pump kick: Interval
Pump kick: Speed
Fig. 83: Pump kick
14.2

Ramp times for setpoint change

184
Additional settings
Universal
Display text
1.6.1.2
Pump kick: Interval
1.6.1.3
Pump kick: Speed
1.6.2
Ramp times
1.6.2.1
Ramp times: Start-up time
1.6.2.2
Ramp times: Switch-off period
1.6.4
Automatic PWM
frequency reduction
OFF
Switched off
ON
Switched on
In order to prevent blocking of the pump, a pump kick is set on the pump. After a set
time interval, the pump starts and switches off after a short time.
Prerequisite:
For the pump kick function, the mains voltage must not be interrupted.
CAUTION
Blockage of the pump due to long downtimes!
Long downtimes may lead to blockage of the pump. Do not deactivate pump kick!
Via remote control, bus command, control input EXT. OFF or 0 ... 10 V signal, pumps
that have been switched off start up briefly. This prevents blockage after long down-
times.
In the menu
"Settings", "Additional settings"
ƒ
The pump kick can be switched on and off.
ƒ
The time interval for the pump kick can be set between 2 and 72 hours (for factory
setting see "Factory setting" [} 191] section).
ƒ
The pump speed at which the pump kick is carried out can be set
Universal
Display text
1.0
Settings
1.6
Additional settings
1.6.1
Pump kick
1.6.1.1
Pump kick: ON/OFF
1.6.1.2
Pump kick: Interval
1.6.1.3
Pump kick: Speed
NOTICE
If a mains disconnection is planned for a longer period of time, the pump kick must
be taken over by an external control by briefly switching on the mains voltage.
For this purpose, the pump must be switched on at the control side before the mains
disconnection.
The ramp times of the pumps can be set in the menu
tings".
"Settings", "Additional set-
WILO SE 2022-05

Advertisement

Table of Contents
loading

This manual is also suitable for:

Yonos giga2.0-d

Table of Contents